M-system R7L-RS4 Instruction Manual page 13

Rtd input module, 4 points (lonworks)
Hide thumbs Also See for R7L-RS4:
Table of Contents

Advertisement

■ FUNCTIONAL BLOCK: fbARM[0...3]
nv 76
...nv 79
• Network Variables
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_lev_percent}
{-163.840...163.835}
{0.0}
{SNVT_temp}
{-274.0...6279.5}
{0.0}
nviARMIn
{SNVT_temp_p}
{-273.17...327.66}
{0.0}
{SNVT_count_32}
{0...999 999 999}
{0}
{SNVT_switch}
nvoARM1
{0.0 0}, {100.0 1}
{0.0 -1}
{SNVT_switch}
nvoARM2
{0.0 0}, {100.0 1}
{0.0 -1}
{SNVT_switch}
nvoARM3
{0.0 0}, {100.0 1}
{0.0 -1}
{SNVT_switch}
nvoARM4
{0.0 0}, {100.0 1}
{0.0 -1}
fbARM[0...3] (Object ID : 33...36)
Network Variables
nviARMIn
SNVT_lev_percent
SNVT_temp
SNVT_temp_p
SNVT_count_32
Configuration Properties
nviARMIn :
SCPTnumDigits
Set the value source
SCPTnvType
Network variable type
SCPTsetpoint[ ]
Alarm setpoint
SCPToffset
Alarm deadband
EXPLANATIONS
Inputs the value to be compared to the alarm setpoint.
nviARMIn alarm 1 (HH)
{100.0 1} with nviARMIn ≥ SCPTsetpoint[0]
Reset to {0.0 0} from {100.0 1} with nviARMIn < (SCPTsetpoint[0] – SCP-
Toffset)
nviARMIn alarm 2 (H)
{100.0 1} with nviARMIn ≥ SCPTsetpoint[1]
Reset to {0.0 0} from {100.0 1} with nviARMIn < (SCPTsetpoint[1] – SCP-
Toffset)
nviARMIn alarm 3 (L)
{100.0 1} with nviARMIn ≤ SCPTsetpoint[2]
Reset to {0.0 0} from {100.0 1} with nviARMIn > (SCPTsetpoint[2] + SCP-
Toffset)
nviARMIn alarm 4 (LL)
{100.0 1} with nviARMIn ≤ SCPTsetpoint[3]
Reset to {0.0 0} from {100.0 1} with nviARMIn > (SCPTsetpoint[3] + SCP-
Toffset)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
nvoARM1
nv 80
SNVT_switch
...nv 83
nvoARM2
nv 84
SNVT_switch
...nv 87
nvoARM3
nv 88
SNVT_switch
...nv 91
nvoARM4
nv 92
SNVT_switch
...nv 95
R7L-RS4
EM-7804-C Rev.5 P. 13 / 19

Advertisement