Modbus Features

MODBUS FEATURES

Supported Modbus Functions

The R9120-5 transceiver responds to the following Modbus query functions:
0x11 Report slave id
0x03 read holding registers (multiple) 0x06 preset single register
These should be sufficient to perform all operations (read many values, make single change, and identify) In addition, the
device will respond to with Modbus exceptions for invalid function, value, and register if out-of-bound requests are made
Modbus function 0x11 Slave ID function will respond with ID=49 "Badger Meter, ModHopper, R9120-5"

Modbus Register List

All Modbus registers are read-only, unless otherwise noted
Data Points
offset
point
type
-------
-------
-------
0
40001
UINT32
1
40002
UINT32
2
40003
UINT32
3
40004
UINT32
4
40005
UINT16
5
40006
UINT16
6
40007
UINT16
7
40008
UINT16
8
40009
UINT16
9
40010
UINT16
10
40011
UNIT16
100
40101
UINT16
101
40102
UINT16
102
40103
UINT16
103
40104
UINT16
104
40105
UINT16
105
40106
UINT32
106
40107
UINT32
107
40108
UINT16
108
40109
UINT16
109
40110
UINT16
110
40111
UINT32
111
40112
UINT32
112
40113
UINT16
113
40114
UINT16
114
40115
UINT16
115
40116
UINT16
116
40117
UINT16
117
40118
UINT16
offset
point
type
------- -------
-------
118
40119
UINT16
119
40120
UINT16
120
40121
UINT16
121
40122
UINT16
122
40123
UINT16
123
40124
UINT16
124
40125
UINT16
125
40126
UINT16
126
40127
UINT16
127
40128
UINT16
128
40129
UINT16
129
40130
UINT16
130
40131
UINT16
131
40132
UINT16
132
40133
UINT16
133
40134
UINT16
134
40135
UINT16
Page 10
desc
------------------
N/V) pulse count 1 MSW
N/V) pulse count 1 LSW
N/V) pulse count 2 MSW
N/V) pulse count 2 LSW(same format as pulse
inst pulse 1 time (seconds)
inst pulse 2 time (seconds)
(R/W) min pulse 1 time (seconds)(write clears min/max)
(R/W) min pulse 2 time (seconds)
(R/W) max pulse 1 time (seconds)
(R/W) max pulse 2 time (seconds)
(R/W, N/V) inst pulse count size. (default 5)
Serial Number (bytes 1,2) (serial number)
Serial Number (bytes 3,4)
Serial Number (bytes 5,6)
firmware version (e.g. v1.03, high byte=major,
lowbyte=minor, 0x8000 flag set for Beta)
boot count
mfg date MSW
mfg date LSW
radio group id setting (0-6)
alarm flags
(0x01 = boot from watchdog)
max packet buffers used.
Radio up time (seconds) MSW
Radio up time (seconds) LSW
RF short packets. write 0 to clear stat counters.
(R/W firmware 1.17 or later)
RS485 short packets
RF Overrun packets
RS485 Overrun packets
RF Timeout packets
RS485 Timeout packets
desc
------------------
RF BadChecksum packets
RS485 BadChecksum packets
RF RX Good packets
RS485 RX Good packets
RF TX packets
RS485 T Good packets
RF TX resend packets
RS485 TX resend packets
RF RouteChange packets
RS485 RouteChange packets
Number of known nodes. (including ourselves)
Our modbus address
R9120 Hardware Version (0=rev-A, 1=rev-B, etc)
Model number
bytes 1,2 (4 registers = 8 char string)
Model number
bytes 3,4 (4 registers = 8 char string)
Model number
bytes 5,6 (4 registers = 8 char string)
Model number
bytes 7,8 (4 registers = 8 char string)
XMT-UM-02107-EN-01