Panasonic SF4D-A18 Instruction Manual page 131

Safety light curtain type 4
Hide thumbs Also See for SF4D-A18:
Table of Contents

Advertisement

["
", "
" blinks]
Control output (OSSD 1 /
2) error.
[" " blinks]
Error in wiring of output
polarity setting / lockout
release input wire (pale
blue).
[" " blinks]
External device error.
© Panasonic Industrial Devices SUNX Co., Ltd. 2020
Cause
The control output 1 (OSSD 1)
wire (black) or the control out-
put 2 (OSSD 2) wire (white) is
shorted to 0V or +V.
The control output 1 (OSSD 1)
wire (black) and control output 2
(OSSD 2) wire (white) are short-
ed to each other, or to another
input / output wire.
Excessive current is flowing in
the control output 1 (OSSD 1)
wire (black) or control output 2
(OSSD 2) wire (white).
The output polarity setting /
lockout release input wire (pale
blue), and the control output
1 (OSSD 1) wire (black) and
control output 2 (OSSD 2) wire
(white) are not connected cor-
rectly.
Output circuit error.
Output polarity setting / lockout
release input wire (pale blue)
is broken or shorted to another
input / output wire.
Incorrect connection of output
polarity setting / lockout release
input wire (pale blue) of receiver
side of emitter / receiver.
T h e s a f e t y r e -
lay contact has
welded.
T h e r e s p o n s e
When a safety
time of the safety
relay is used
relay is slow.
S a f e t y r e l a y
contact "b" is not
connected.
The auxiliary out-
put wire (red) and
external device
When the ex-
monitor input wire
ternal device
(pale purple) are
monitor func-
not connected.
tion is invalid.
Auxiliary output does
not operate correctly.
Remedy
Connect the control output 1 (OSSD 1) wire
(black) and the control output 2 (OSSD 2) wire
(white) to the safety relay unit, external device
(forcible guide relay or magnetic contactor), safety
controller, or safety PLC.
The current values of the control output 1 (OSSD
1) wire (black) and the control output 2 (OSSD 2)
wire (white) must be within the specified range.
<Using PNP output>
• Connect the output polarity setting / lockout re-
lease input wire (pale blue) to 0V (blue).
• Connect the control output 1 (OSSD 1) wire
(black) and the control output 2 (OSSD 2) wire
(white) to the safety relay unit, external device
(forcible guide relay or magnetic contactor),
safety controller, or safety PLC.
<Using NPN output>
• Connect the output polarity setting / lockout re-
lease input wire (pale blue) to + V (brown).
• Connect the control output 1 (OSSD 1) wire
(black) and the control output 2 (OSSD 2) wire
(white) to the safety relay unit, external device
(forcible guide relay or magnetic contactor),
safety controller, or safety PLC.
Output circuit damage. Replace the device.
<Using PNP output>
Connect the output polarity setting / lockout re-
lease input wire (pale blue) to 0V (blue).
<Using NPN output>
Connect the output polarity setting / lockout re-
lease input wire (pale blue) to + V (brown).
Replace the safety relay.
Replace with a safety relay with a suitable re-
sponse time.
Refer to "3-6 External Device Monitor Function
(8-core cable, 12-core cable)".
Correctly connect the safety relay.
Refer to "2-5-7 Wiring Configuration for
Valid External Device Monitor Function
(Example of Control Category 4 Wiring)".
Connect the auxiliary output wire (red) and exter-
nal device monitor input wire (pale purple).
Check if the auxiliary output wire (red) is broken or
has shorted.