Tripp Lite SmartOnline S3MX Owner's Manual page 21

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
4. Operation
Programs Available List for Parameter 1:
Code
Description
01
Output voltage
02
Output frequency
03
Voltage range for bypass
04
Frequency range for bypass
05
ECO Mode enable/disable
06
Voltage range for ECO Mode
07
Frequency range for ECO Mode
08
Bypass Mode setting
09
Maximum battery discharge time setting
10
Reserved
11
Hot standby function setting
12
Neutral loss detection
13
Battery voltage calibration
14
Charger voltage adjustment
15
Inverter A voltage adjustment
16
Inverter B voltage adjustment
17
Inverter C voltage adjustment
18
Output A voltage calibration
19
Output B voltage calibration
20
Output C voltage calibration
21
Charger current setting
22
Charging boards quantity setting
*Y means that this program can be set in this mode.
Note: All parameter settings will be saved only when the UPS shuts down normally with an internal or external battery connection. Normal UPS shutdown
means turning off input breaker in Bypass/No Output Mode.
01: Output Voltage
Interface
No Output mode
Setting
Parameter 3: Output voltage
For 220/230/240V AC models, you may choose the following output voltage:
220: Output voltage is 220V AC.
230: Output voltage is 230V AC (Default).
240: Output voltage is 240V AC.
Bypass /
AC
Mode
Y*
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Reserved for future options
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
21
ECO
CVCF
Battery
Mode
Mode
Mode
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Battery
Test
Y
Y
Y
Y

Advertisement

Table of Contents
loading

Table of Contents