Tripp Lite SmartOnline S3MX Owner's Manual page 23

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
4. Operation
06: Voltage Range for ECO Mode
Interface
07: Frequency Range for ECO Mode
Interface
08: Bypass Mode Setting
Interface
09: Maximum Battery Discharge Time Setting
Interface
10: Reserved
Interface
Setting
Parameter 2: Low voltage point in ECO Mode. The setting range is from -5% to -10% of the
nominal voltage.
Parameter 3: High voltage point in ECO Mode. The setting range is from +5% to +10% of the
nominal voltage.
Setting
Parameter 2: Set the low frequency point for ECO Mode.
50 Hz system: Setting range is from 46.0 Hz to 48.0 Hz.
60 Hz system: Setting range is from 56.0 Hz to 58.0 Hz.
The default value is 48.0 Hz/58.0 Hz.
Parameter 3: Set high frequency point for ECO Mode.
50 Hz: Setting range is from 52.0 Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0 Hz to 64.0 Hz.
The default value is 52.0 Hz/62.0 Hz.
Setting
Parameter 2:
OPN: Bypass allowed. When selected, the UPS will run in Bypass Mode depending on whether the
bypass setting is enabled/disabled.
FBD: Bypass not allowed. When selected, Bypass Mode is not allowed in any situation.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass Mode is activated (Default).
DIS: Bypass disabled. When selected, automatic bypass is acceptable, but manual bypass is
not allowed. Manual bypass means users manually operate UPS for Bypass Mode. For example,
pressing OFF button in AC Mode to turn into Bypass Mode.
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 to 999 min. The UPS will shut down to the
protect battery if the discharge time arrives before the battery is under voltage. The default value is
990 min.
DIS: Disable battery discharge protection and backup time will depend on battery capacity.
Setting
Reserve for future options.
23

Advertisement

Table of Contents
loading

Table of Contents