Indicator Lights (Front Panel)
"ON" Button
To turn the UPS ON:
the button after you hear a beep. If utility power is absent, you can "cold-start" the UPS (i.e.: turn it ON and supply power for a
limited time from its batteries, if they're fully charged) by pressing and holding the "ON" button for one second until you hear a
beep.
To perform a battery test during AC mode:
a beep.
To silence the alarm during On Battery mode:
"OFF/STANDBY" Button
To turn the UPS OFF:
second. Then unplug the UPS from the wall outlet. The UPS will be completely OFF.*
* After you plug the UPS into a live AC outlet, the UPS will automatically charge its batteries and will supply power to its outlets unless the unit is turned OFF.
"Overload" LED: if this light is illuminated, the load is >105%. Clear the overload immediately by unplugging some of your
equipment from the outlets until the LEDs on the Load Level graph change to yellow (100% load) or green (20 to 80% load).
CAUTION! Any overload that is not immediately corrected by the user may cause the UPS to shut down and cease
supplying output power in the event of a blackout or brownout.
"Automatic Voltage Regulation" (AVR) mode LED: if the UPS is operating in AVR mode, this yellow light will be illuminated.
The UPS will boost or trim the input voltage to regulate the output voltage.
"AC mode" LED: if the input voltage is within acceptable range, this green LED will be illuminated.
"UPS Fault" LED: this red LED is illuminated when there is an internal fault in the UPS.
"Site Wiring Fault" LED: this red LED will illuminate when the UPS senses a site wiring problem.
"Battery Fault" LED: when the unit senses a weak, bad or disconnected battery, this yellow light will illuminate.
"On Battery" mode LED: if UPS is operating from battery power, this green light will be illuminated.
"Load Level" LED: During AC mode, this green light will illuminate and the LED bars will indicate the level of output load.
"Battery Capacity" LED: During battery mode or battery test mode, this green light will illuminate and the LED bars will
indicate the battery capacity.
with the UPS plugged into a live AC wall outlet, press and hold the "ON" button for one second. Release
press and hold the "ON" button for one second. Release the button after you hear
press and hold the "ON" button for one second. Release the button.
with the UPS ON and receiving utility power, press and hold the "OFF/STANDBY" button for one