LG MULTI V S ARUN030GSS0 Installation Manual page 32

Hide thumbs Also See for MULTI V S ARUN030GSS0:
Table of Contents

Advertisement

1,MFL67798030,영영 2018. 12. 7. 영영 1:37 Page 32
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
32
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity (HP)
Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit
total capacity [kW(Btu/h)]
≤ 5.6(19,100)
< 16.0(54,600)
≤ 22.4(76,400)
< 36.4(124,200)
WARNING
!
When the any one (or both ) of below conditions are satisfied, the diameter of main pipe (A)
must be increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90m or more
(Liquid and Gas pipes are increased)
- The level difference (Outdoor unit ÷ Indoor unit) is 50m or more (Only liquid pipe is
increased)
Liquid pipe [mm(inch)]
4
5
6
8
10
12
Liquid pipe [mm(inch)]
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø6.35(1/4)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Gas pipe [mm(inch)]
Ø15.88(5/8)
Ø15.88(5/8)
Ø19.05(3/4)
Ø19.05(3/4)
Ø22.2(7/8)
Ø28.58(11/8)
Gas pipe [mm(inch)]
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)

Advertisement

Table of Contents
loading

Table of Contents