Rinnai ThermaCirc360 RUR199i Installation And Operation Manual page 52

Tankless water heater
Table of Contents

Advertisement

5
PRESSURE RELIEF VALVE (PRV)
Does the PRV comply with the standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water
Supply Systems ANSI Z21.22, and/or the standard Temperature, Pressure, Temperature and Pressure Relief
Valves and Vacuum Relief Valves, CAN1-4.4?
Did you verify the PRV is rated up to 150 psi and (at least) the maximum BTU/hr of the water heater?
Is the discharge from the PRV piped to the ground or into a drain system as per local codes?
Is the discharge line from the PRV pitched downward and does it terminate 6 in. (152 mm) above the drains?
Is the discharge end of the line plain (unthreaded) and a minimum of 3/4 in. diameter?
Is the discharge line material suitable for at least 180° F water?
Did you take measures to protect the PRV and PRV discharge line from freezing?
Have you verified the PRV is not plumbed with the condensate drain line?
Have you verified the PRV is not plugged and that reducing fittings, valves, or other restrictions are not
installed in the relief line?
6
CONDENSATE DRAIN
If the condensate pump is installed, is it wired to deactivate the tankless water heater in the event of failure?
For more information, refer to the "Condensate Pump Safety Switch Wiring" section of the manual.
Did you verify the condensate drain pipe is as short as possible and has a downward pitch toward the drain or
condensate pump?
Is all condensate drained and disposed of as per local codes?
Did you use ONLY corrosion resistant materials for the condensate drain lines?
Did you verify the condensate drain pipe along its entire length is at least the same diameter as the drain line
(1/2 in. NPT)?
Did you check to ensure the condensation drain lines are protected from freezing?
If a floor pump is not available or the drain is above the level of the condensate drain, did you install a
condensate pump?
Have you verified the condensate drain line is not plumbed with the pressure relief valve?
Have you confirmed the condensate drain line is not connected with an air conditioning evaporator coil drain?
Have you verified an external condensate trap is not installed? (This tankless water heater has an integrated
condensate trap.)
Have you confirmed the end of the condensate drain pipe is open to atmosphere?
7
GAS SUPPLY
Did you verify the gas system is appropriately sized?
Did you verify the water heater is rated for the gas type supplied?
Have you performed a gas line and connection leak test?
Did you install a manual gas control valve in the gas line to the water heater?
Is the inlet gas pressure within limits?
Did you purge the gas line of any debris before connecting the water heater?
RECIRCULATION PUMP SE+ Series Featuring ThermaCirc360™ Models Only
8
(RUR199i/RUR199e and RUR160i/RUR160e)
Have parameter settings for recirculation been properly set?
Is the recirculation pipe length less than the maximum allowed length?
Did you drain the tankless water heater if not intended to be used immediately?
Did you install an MC-195T or Control-R™ Wi-Fi controller to program the recirculation pump?
Have you performed a leak and pressure test on the crossover valve installation?
(Crossover Mode Only) Was the crossover valve installed at the furthest fixture from the water heater?
(Crossover Mode Only) Did you remove the bypass plug
and replace it with the bypass filter?
52
Remove
Bypass Plug
Rinnai Tankless Water Heater Installation and Operation Manual
Replace with
Bypass Filter
YES NO
YES NO
YES NO
YES NO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents