K8AK-AW
Example Relay Sequence for Overcurrent/Undercurrent Monitoring Mode
<Explanation of operation>
• RY2 (magnet contactor) will be energized in approx. 100 ms when PB1 (startup button) is pressed.
• Use a timer for the K8AK undercurrent alarm (AL2) as a switch from contact "b" to contact "a" will not occur for approx. 250 ms even if the magnet
contactor (RY2) is turned on.
<Timer setting conditions (reference)>
• TA
: Timer (H3YN-2 + socket, Omron)
• Operating mode : Interval mode
• Setting time
: 2 s
Before pressing the startup button (after approx. 1.25 seconds have passed following turning on the power supply of K8AK)
A1
A2
Magnet contactor for load switching OFF
Immediately after pressing the startup button (within approx. 250 ms)
A1
A2
Magnet contactor for load switching ON
Two seconds after pressing the startup button
A1
A2
Magnet contactor for load switching ON
Note: 1. K8AK output contacts will operate (contact "a") within the setting range for current input values (normal status).
2. The overcurrent alarm (AL1) and undercurrent alarm (AL2) will operate as follows before the magnet contactor (RY2) is turned on (state
without current input).
• Overcurrent alarm (AL1): Contact "b" for the approx. 1 second interval immediately after the K8AK control power supply is turned on. After that, a switch
• Undercurrent alarm (AL2): Contact "b" for the approx. 1 second interval immediately after the K8AK control power supply is turned on. After that, because
6
Load
RY2
K8AK
Load
RY2
K8AK
Load
RY2
K8AK
to contact "a" will be made as an overcurrent state is no longer present. At that time, there will be a response delay time from
contact "b" to contact "a" of approx. 250 ms.
a state without current input will continue, an undercurrent will be detected and the status of contact "b" will continue as is.
Startup button
PB1
RY1
A1
Stop button
PB2
K8AK
A2
T
RY1
A
Startup button
PB1
RY1
A1
Stop button
PB2
K8AK
A2
T
RY1
A
Startup button
PB1
RY1
A1
Stop button
PB2
K8AK
A2
T
RY1
A
AL1: K8AK overcurrent contacts
11
AL2: K8AK undercurrent contacts
AL1
14
21
AL2
T
A
24
RY1
RY2
AL1: K8AK overcurrent contacts
11
AL2: K8AK undercurrent contacts
AL1
14
21
AL2
T
A
24
RY1
RY2
AL1: K8AK overcurrent contacts
AL2: K8AK undercurrent contacts
11
AL1
14
21
AL2
T
A
24
RY1
RY2