Gas Supply Line
Provide a gas supply line of 3/4" (1.9 cm) rigid pipe to the
■
cooktop location. A smaller size pipe on longer runs may
result in insufficient gas supply. Pipe-joint compounds that
resist the action of Propane gas must be used. Do not use
TEFLON
tape. With Propane gas, piping or tubing size can
®†
be 1/2" (1.6 cm) minimum. Usually, Propane gas suppliers
determine the size and materials used in the system.
Flexible metal appliance connector:
If local codes permit, use a 5/8" (1.6 cm) flexible stainless
■
steel tubing gas connector, designed by CSA to connect
the cooktop to the rigid gas supply line.
NOTE: For multi-unit installations, a single shut-off valve
is acceptable. Each unit must have its own regulator
(supplied with the unit) and flexible stainless steel tubing
gas connector.
A 1/2" (1.3 cm) male pipe thread is needed for
■
connection to the female pipe threads of the inlet
to the appliance pressure regulator.
Do not kink or damage the flexible metal tubing when
■
moving the cooktop.
Must include a shut-off valve:
■
Install a manual gas line shut-off valve in an easily accessible
location. Do not block access to shut-off valve. The valve is
for turning on or shutting off gas to the cooktop.
B
A
A. Gas supply line
B. Shut-off valve open position
C. To cooktop
†
®
TEFLON is a registered trademark of Chemours.
6
The gas pressure regulator supplied with this cooktop must be
used. The inlet pressure to the regulator should be as follows for
proper operation:
Natural Gas:
Minimum pressure: 15.2 cm WCP
Maximum pressure: 35.5 cm WCP
Propane Gas:
Minimum pressure: 27.9 cm WCP
Maximum pressure: 35.5 cm WCP
Contact local gas supplier if you are not sure about the inlet
pressure.
NOTE: For multi-unit installations, each unit must have its own
regulator (supplied with the unit).
Input ratings shown on the model/serial/rating plate are for
elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced
at a rate of 4% for each 1,000 ft (304.8 m) above sea level
(not applicable for Canada).
For elevations above 6,560 ft (1999.5 m), a high altitude kit
is needed to avoid any reduced power output. See separate
Propane gas conversion instructions sheet.
Line pressure testing above 1/2 psi (3.5 kPa) gauge
(35.6 cm WCP)
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psi (3.5 kPa).
Line pressure testing at 1/2 psi (3.5 kPa) gauge
(35.6 cm WCP) or lower
C
The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
Gas Pressure Regulator
Burner Input Requirements
Gas Supply Pressure Testing