Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.
Illustrations show RZQG125L outdoor unit type. Other types
also follow this installation manual.
This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.
Never operate the unit with a damaged or disconnected
discharge thermistor and suction thermistor, burning of the
compressor may result.
Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.
When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.
3.5.
Model identification
RZQG units include special equipment (insulation, optional bottom
plate heater, ...) to ensure good operation in areas where low ambient
temperature can occur together with high humidity conditions. In such
conditions the RZQSG models may experience problems with severe
ice build up on the air-cooled coil. If such conditions are expected, a
RZQG unit must be installed instead. These models contain
countermeasures (insulation, optional bottom plate heater, ...) to
prevent freeze up.
4.

Accessories

Check if the following accessories are included with the unit:
See the figure below for the location of the accessories.
1
2
3
1 Installation manual
2 Clamp
3 Fluorinated greenhouse gases label
4.1.

Handling

As shown in the figure, bring the unit slowly by grabbing the left and
right grips.
Place your hands on the corner instead of holding the suction inlet in
the side of the casing, otherwise the casing could be deformed.
CAUTION
Take care not to let hands or objects come in contact with
rear fins.
RZQG71~140L + RZQSG100~140L7V1+Y1B(9)
Split system air conditioners
4P327537-1 – 2012.08
5.
5.1.
1x

Selecting installation site

General

WARNING
Be sure to provide for adequate measures in order to
prevent that the outdoor unit be used as a shelter by
small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.
Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
-
Places which are well-ventilated.
-
Places where the unit does not bother next-door neighbours.
-
Safe places which can withstand the unit's weight and
vibration and where the unit can be installed level.
-
Places where there is no possibility of flammable gas or
product leak.
-
The equipment is not intended for use in a potentially
explosive atmosphere.
-
Places where servicing space can be well ensured.
-
Places where the indoor and outdoor units' piping and wiring
lengths come within the allowable ranges.
-
Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
-
Places where the rain can be avoided as much as possible.
-
Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a
lot of dust is created, the unit must be covered.
-
Do not place any objects or equipment on top of the unit (top
plate).
-
Do not climb, sit or stand on top of the unit,
-
Be sure that sufficient precautions are taken, in accordance
with applicable legislation, in case of refrigerant leakage.
NOTICE
This is a class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
-
Deterioration of the operational capacity.
-
Frequent frost acceleration in heating operation.
-
Disruption of operation due to rise of high pressure.
-
When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.