Mitsubishi Electric CITY MULTI Data Book page 44

Air conditioning systems
Hide thumbs Also See for CITY MULTI:
Table of Contents

Advertisement

1. SPECIFICATIONS
Heat Source Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
cooling
Inlet water
Heating capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
heating
Inlet water
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room)
Refrigerant
Liquid pipe
piping diameter
Gas pipe
Set Model
Model
Minimum Circuit Ampacity
Maximum Overcurrent Protection
Circulating water
Water flow rate
Pressure drop
Operating volume
range
Compressor
Type x Quantity
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit
Compressor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
Water volume in plate
Water pressure Max.
HIC circuit (HIC: Heat Inter-Changer)
Pipe between unit and
Liquid pipe
distributor
Gas pipe
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.<Standard CITY MULTI indoor unit> Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 81°FD.B./66°FW.B. (27°CD.B./19°CW.B.), Inlet water temperature: 86°F (30°C), Brine concentration 0%
2.<PWFY-P36/72NMU-E2-AU> Nominal cooling conditions
Inlet water Temp.: 86°F (30°C), Pipe length: 25 ft. (7.6 m), Level difference: 0 ft. (0 m),
Inlet water Temp.: 73°F (23°C), Water flow rate: 1.93 m
Brine concentration 0%
3.<Standard CITY MULTI indoor unit> Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 68°FD.B.(20°CD.B.), Inlet water temperature: 68°F (20°C), Brine concentration 0%
4.<PWFY-P36/72NMU-E2-AU> Nominal heating conditions
Inlet water Temp.: 68°F (20°C), Pipe length: 25 ft. (7.6 m), Level difference: 0 ft. (0 m),
Inlet water Temp.: 86°F (30°C), Water flow rate: 2.15 m
Brine concentration 0%
MEES19K187
*1, 2
BTU/h
kW
kW
A
BTU/h
kW
kW
A
W.B.
ºF
*3, 4
BTU/h
kW
kW
A
BTU/h
kW
kW
A
D.B.
ºF
dB <A>
in. (mm)
in. (mm)
PQHY-P168YLMU-A1 < For Ground source >
A
A
G/h
G/min (gpm)
3
m
/h
L/min
cfm
psi
kPa
G/h
G/min (gpm)
3
m
/h
Inverter scroll hermetic compressor x 1
kW
kW
Galvanized steel sheets
in.
57-1/8 x 34-11/16 x 21-11/16
mm
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
Over-heat protection
R410A x 13 lbs + 4 oz (6.0 kg)
lbs (kg)
G
l
psi
MPa
Copper pipe, tube-in-tube structure
in. (mm)
in. (mm)
1-1/8 (28.58) Brazed
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation
Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the Heat Source Unit needs to be kept below 104°FD.B. (40°CD.B.)
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
The cooling tower and the water circuit must be a closed circuit (water is not exposed to the atmosphere).
Add brine to circulating water when a unit is operating at water temperature below 50°F (10°C), and turn DipSW4 (773) ON before power ON.
It is recommended to set the brine concentration to a percentage that will keep the freezing temperature at -15°C or less.
3
3
/h (8.3 gpm) <P36>/3.86 m
/h (16.6 gpm) <P72>,
3
3
/h (9.2 gpm) <P36>/4.30 m
/h (18.5 gpm) <P72>,
PQHY-P312YSLMU-A1 < For Ground source >
Non-Ducted
3-phase 3-wire 460 V ±10% 60 Hz
312,000
91.4
23.41
32.6
297,000
87.0
21.59
30.1
59~75°F (15~24°C)
23~113°F (-5~45°C)
350,000
102.6
19.11
26.6
334,000
97.9
17.62
24.5
59~81°F (15~27°C)
23~113°F (-5~45°C)
50~130% of heatsource unit capacity
P04~P96/2~50
58.0
3/4 (19.05) Brazed
1-3/8 (34.93) Brazed
20
35
1,902 + 1,902
31.7 + 31.7
7.20 + 7.20
120 + 120
4.2 + 4.2
6.38
44
1,189 + 1,189 ~ 3,054 + 3,054
19.8 + 19.8 ~ 50.9 + 50.9
4.5 + 4.5 ~ 11.6 + 11.6
Inverter
11.0
-
MEL32
1,450 x 880 x 550
LEV and HIC circuit
501 (227)
plate type
1.32
5.0
290
2.0
5/8 (15.88) Brazed
KL94C238
KE94G419
Installation Manual
Details refer to External Drw
Heat Source Twinning kit: CMY-Y200CBK2
joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-Y202S-G2, CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Ducted
23.67
33.0
17.96
25.0
PQHY-P144YLMU-A1 < For Ground source >
16
25
6.38
44
Inverter scroll hermetic compressor x 1
Inverter
9.5
-
MEL32
Galvanized steel sheets
57-1/8 x 34-11/16 x 21-11/16
1,450 x 880 x 550
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
Over-heat protection
R410A x 13 lbs + 4 oz (6.0 kg)
501 (227)
plate type
1.32
5.0
290
2.0
Copper pipe, tube-in-tube structure
5/8 (15.88) Brazed
1-1/8 (28.58) Brazed
KE94G419
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
WY-Series
33

Advertisement

Table of Contents
loading

Table of Contents