Mitsubishi Electric CITY MULTI Data Book page 175

Air conditioning systems
Hide thumbs Also See for CITY MULTI:
Table of Contents

Advertisement

7. CAPACITY TABLES
7-3-2. Heating capacity correction
PQHY-P72ZLMU
1.00
0.90
0.80
0
100
200
Piping equivalent length
PQHY-P96, 120ZLMU
1.00
0.90
0.80
0
100
200
Piping equivalent length
PQHY-P144, 168, 192, 216, 240Z(S)LMU
1.00
0.90
0.80
0
100
200
Piping equivalent length
7-3-3. How to obtain the equivalent piping length
1. PQHY-P72ZLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.15 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bent on the piping) [m]
2. PQHY-P96, 120ZLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.38 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bent on the piping) [m]
3. PQHY-P144, 168, 192, 216, 240Z(S)LMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bent on the piping) [m]
4. PQHY-P288, 312ZSLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (2.30 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bent on the piping) [m]
5. PQHY-P336, 360ZSLMU
Equivalent length = (Actual piping length to the farthest indoor unit) + (2.63 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bent on the piping) [m]
MEES19K187
300
400
500
600
300
400
500
600
300
400
500
600
PQHY-P288, 312ZSLMU
1.00
0.90
0.80
ft.
0
100
200
PQHY-P336, 360ZSLMU
1.00
0.90
0.80
ft.
0
100
200
ft.
WY-Series-575V
300
400
500
Piping equivalent length
300
400
500
Piping equivalent length
600
ft.
600
ft.
164

Advertisement

Table of Contents
loading