5. TRANSPORT
5.1. TRANSPORT DAMAGE
You must immediately check the shipment to make sure it is undamaged and complete and must do so in
the presence of the supplier. In the case of transport damage, contact the service department for advice (see
contents).
The fan units can be shipped in their original packaging (on 1 pallet and plastic-wrapped).
The fan units must be transported in accordance with the applicable guidelines/standards.
Unprofessional transport such as setting the product down too hard or on its side can lead to:
- the impeller becoming jammed in the fan unit or being thrown off balance,
- misaligning of the shafts,
- damage to the bearings,
- damage to electrical components,
- damage to the paint.
5.2. TRANSPORT SAFETY
The transport device must be suitable for lifting the weight of the pallet (meaning the fan units plus packaging).
The fan units can be shipped in their original packaging (on 1 pallet and plastic-wrapped). Once on location,
position the units as close as possible to the place where they will be installed.
The following can act as leverage points for the fan unit:
1. Pallet (if still in original packaging)
2. Mounting plate
No other options for lifting the product are permitted.
The following leverage points are unsuitable:
- packaging
- the grid
- the fan unit's outlet opening,
- any operational switch, frequency regulator or outer terminal box that may be installed.
5.3. TEMPORARY STORAGE
For temporary storage of the fan unit, the following points must be strictly adhered to:
- Humidity 50% and temperature between 5º C and 60º C, free of dust, dirt, gasses and corrosive atmosphere
- It is recommended to store the fan not longer than 12 months after delivery
- Before installation check the motor bearing