Schumacher Electric EV Series Installation And User Manual page 14

Table of Contents

Advertisement

FINAL STEPS
Dedicated
Breaker
Kilowatts
20A
3.8kW
30A
5.8kW
40A
7.7kW
50A
9.6kW
60A
11.5kW
70A
12.0kW
80A
12.0kW
For models SEV1600HW, SEV1600P1450, and SEV1600P650, the
following steps must be completed by a licensed electrician.
1.
Before starting, the licensed electrician should consult all applicable
codes for breaker and wire sizing requirements. Set the amperage of
the unit according to the connected dedicated breaker associated
with the hardwired connection or NEMA outlet. Using the table above,
determine the voltage and amperage of the installation. Then, set
the unit's DIP switch following the diagram below that corresponds
with the dedicated breaker's voltage and amperage and the model's
requirements.
20A BREAKER 240V 16A
50A BREAKER 240V 40A
80A BREAKER 240V 50A**
Voltage
208V/240V
208V/240V
208V/240V
208V/240V
208V/240V
208V/240V
208V/240V
30A BREAKER 240V 24A
60A BREAKER 240V 48A**
* All models' default current settings are set to 32A.
**Models SEV1600P1450 and SEV1600P650 should
not use a current setting greater than 40A.
- 14 -
Amperage Hardwired
16A
Y
24A
Y
32A
Y
40A
Y
48A
Y
50A
Y
50A
Y
40A BREAKER 240V 32A*
Factory setting
70A BREAKER 240V 50A**
Plug
Y
Y
Y
Y
N
N
N