DOMESTIC UNITS — Standard 09DP unit packaging con-
sists of coil protection only. Skids are not provided. If overhead
rigging is not available at the jobsite, place the unit on a skid or
pad before dragging or rolling. When rolling, use a minimum
of 3 rollers. When dragging, pull the pad or skid. Do not apply
force to the unit. When in final position, raise from above to lift
unit off the pad or skid.
EXPORT UNITS — All export units are mounted on skids
with vertical coil protection. Leave the unit on the skid until it
is in final position. While on the skid, the unit can be rolled or
skidded. Apply force to the skid, not to the unit. Use a mini-
mum of 3 rollers when rolling. When in final position, raise
from above to remove the skid.
PLACING UNITS — When considering location of the unit,
be sure to consult National Electrical Code (NEC, U.S.A.) and
local code requirements. Allow sufficient space for airflow,
wiring, piping, and service. The placement area must be level
and strong enough to support the operating weight of the unit.
(See Fig. 2.) When unit is in proper location, use of mounting
09DP Unit (lb)
09DP
OPERATIONAL CORNER WEIGHT
TOTAL
UNIT
WEIGHT
A
SIZE
018
638
153
020
719
173
030
869
208
035
1126
290
040
1204
319
050
1282
331
060
1524
392
065
1622
413
075
1846
471
085
1933
493
095
1933
493
115
2447
418
130
2533
429
B
C
a09-584
A
D
TOP VIEW,
SIZES 018 TO 030
B
C
D
E
F
149
166
171
169
186
191
203
226
231
289
273
274
317
283
285
329
310
312
390
370
372
409
398
403
465
452
457
487
474
479
487
474
479
414
397
402
405
410
424
416
420
420
425
B
A
TOP VIEW, SIZES 035 TO 060
Fig. 2 — Corner Weights
holes in base rails is recommended for securing unit to
supporting structure. Fasteners for mounting unit are field sup-
plied. See Fig. 4.
Refer to Fig. 5-9 for airflow clearances. Recommended
minimum clearances are 6 ft (1829 mm) for unrestricted air-
flow and service on sides of unit, 4 ft (1219 mm) on ends, and
unrestricted clear air space above the unit. Provide ample space
to connect refrigerant lines to indoor unit. For multiple units,
allow 10 ft (3048 mm) separation between airflow surfaces. If
walls surround the unit, wall height should not exceed the top
of the unit fan discharge. Installation in a pit is not recommend-
ed.
IMPORTANT: Be sure to mount unit level to ensure
proper oil return to compressors.
Refer to Fig. 10 for outdoor fan and compressor layout.
Refer to Fig. 11 and 12 for unit piping installation.
09DP Unit (kg)
09DP
TOTAL
UNIT
WEIGHT
SIZE
018
289
020
326
030
394
035
511
132
040
546
145
050
582
150
060
691
178
065
736
187
075
837
214
085
877
224
095
877
224
115
1110
285
130
1149
292
C
B
D
A
TOP VIEW, SIZES 065 TO 130
9
OPERATIONAL CORNER WEIGHT
A
B
C
D
E
69
67
75
77
79
77
84
87
94
92
103
105
131
124
124
144
128
129
149
141
141
177
168
169
185
181
183
211
205
207
221
215
217
221
215
217
282
270
273
250
289
283
286
262
E
F
F
248
258
C
D

Advertisement

Table of Contents
loading

Table of Contents