Carrier GEMINI 09DPS018 Installation, Start-Up And Maintenance Instructions
Carrier GEMINI 09DPS018 Installation, Start-Up And Maintenance Instructions

Carrier GEMINI 09DPS018 Installation, Start-Up And Maintenance Instructions

Air-cooled condensing units

Advertisement

Quick Links

Installation, Start-Up and Maintenance
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-36
Step 1 - Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• GENERAL
• GENERAL
Step 5 - Check Condenser Fans. . . . . . . . . . . . . . . . 30
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Step 7 - Install Accessories . . . . . . . . . . . . . . . . . . . . 34
• LOW-AMBIENT OPERATION
• MISCELLANEOUS ACCESSORIES
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37,38
System Evacuation and Dehydration . . . . . . . . . . . . 37
Preliminary Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Adjust Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . 37
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . 37
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Recommended Maintenance Schedule . . . . . . . . . . 39
Condenser Coil Maintenance and Cleaning
Recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func-
tions, such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in the
literature, and on tags, stickers, and labels attached to the
equipment and any other safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-530900013-01
Instructions
Page
®
V
Printed in U.S.A.
Form 09DP-3SI
09DPS018-030, 09DPM035-130
Air-Cooled Condensing Units
• Use care in handling, rigging, and setting bulky
equipment.
Open all remote disconnects before servicing this equip-
ment. Failure to do so could result in personal injury from
electric shock.
Separate power sources (main and control power circuits)
are used for these units. Be sure both main and control
power circuits are disconnected before servicing. Failure to
do so could result in personal injury from electric shock.
o
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog-
gles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig-
erant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
o
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these proce-
dures may result in damage to equipment.
Pg 1
GEMINI™ SELECT
50/60 Hz
WARNING
DANGER
WARNING
CAUTION
612
9-11
Replaces: 09DP-1SI

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GEMINI 09DPS018 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier GEMINI 09DPS018

  • Page 1: Table Of Contents

    GEMINI™ SELECT 09DPS018-030, 09DPM035-130 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Maintenance Instructions CONTENTS • Use care in handling, rigging, and setting bulky equipment. Page SAFETY CONSIDERATIONS ..... . 1 WARNING INSTALLATION .
  • Page 2: Installation

    INSTALLATION Step 1 — Inspect Shipment — Inspect unit for dam- CAUTION age upon arrival. If damage is found, immediately file a claim with the shipping company. Verify proper unit delivery by All panels must be in place when rigging. Failure to com- checking unit nameplate data and the model number nomen- ply could result in equipment damage.
  • Page 3 Table 1 — Physical Data, 09DP018-040 Units — English 09DP UNIT SIZE 09DPS018 09DPS020 09DPS030 09DPM035 09DPM040 20.7 33.1 37.7 43.3 55.0 CAPACITY, 60 Hz (tons)* 17.2 27.6 31.4 36.1 45.8 CAPACITY, 50 Hz (tons)* Single Circuit Single Circuit Single Circuit Dual Circuit Single Circuit Dual Circuit Single Circuit CIRCUIT OPERATING WEIGHTS (lb) Standard...
  • Page 4 Table 2 — Physical Data, 09DP050-075 Units — English 09DP UNIT SIZE 09DPM050 09DPM060 09DPM065 09DPM075 66.4 75.3 85.8 107.6 CAPACITY, 60 Hz (tons)* 55.3 62.7 71.5 89.7 CAPACITY, 50 Hz (tons)* Dual Single Dual Single Dual Single Dual Single CIRCUIT Circuit Circuit...
  • Page 5 Table 3 — Physical Data, 09DP085-130 Units — English 09DPM085 09DPM095 09DPM115 09DPM130 09DP UNIT SIZE 115.6 129.4 149.4 172.0 CAPACITY, 60 Hz (tons)* 96.3 107.8 124.5 143.3 CAPACITY, 50 Hz (tons)* Dual Single Dual Single Dual Single Dual Single CIRCUIT Circuit Circuit...
  • Page 6 Table 4 — Physical Data, 09DP018-040 Units — SI 09DPS018 09DPS020 09DPS030 09DPM035 09DPM040 09DP UNIT SIZE 72.8 116.4 132.6 152.3 193.4 CAPACITY, 60 Hz (kW)* 60.7 97.0 110.5 126.9 161.2 CAPACITY, 50 Hz (kW)* Single Circuit Single Circuit Single Circuit Dual Circuit Single Circuit Dual Circuit Single Circuit CIRCUIT OPERATING WEIGHTS (kg) Standard...
  • Page 7 Table 5 — Physical Data, 09DP050-075 Units — SI 09DPM050 09DPM060 09DPM065 09DPM075 09DP UNIT SIZE 233.5 264.8 301.8 378.5 CAPACITY, 60 Hz (kW)* 194.6 220.7 251.5 315.4 CAPACITY, 50 Hz (kW)* Dual Single Dual Single Dual Single Dual Single CIRCUIT Circuit Circuit...
  • Page 8 Table 6 — Physical Data, 09DP085-130 Units — SI 09DP UNIT SIZE 09DPM085 09DPM095 09DPM115 09DPM130 CAPACITY, 60 Hz (kW)* 406.6 455.1 525.5 605.0 CAPACITY, 50 Hz (kW)* 338.8 379.2 437.9 504.2 Dual Single Dual Single Dual Single Dual Single CIRCUIT Circuit Circuit...
  • Page 9: Domestic Units

    DOMESTIC UNITS — Standard 09DP unit packaging con- holes in base rails is recommended for securing unit to sists of coil protection only. Skids are not provided. If overhead supporting structure. Fasteners for mounting unit are field sup- rigging is not available at the jobsite, place the unit on a skid or plied.
  • Page 10 SIZES 018 TO 060 SIZES 065 TO 130 a09-585 a09-586 Fig. 3 — Rigging Labels a09-587 Fig. 4 — Perimeter Support Channel...
  • Page 11 a09-576...
  • Page 12 a09-611 a09-611...
  • Page 13 a09-612...
  • Page 14 a09-613...
  • Page 15 a09-614...
  • Page 16 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM3 OFM3 OFM3 OFM3 OFM3 OFM3 OFM3 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM1 OFM2 OFM2 OFM2 OFM2 OFM2 OFM2 OFM3 OFM2...
  • Page 17 3. All wiring must comply with applicable local and national codes. FIELD 4. All piping must follow standard piping techniques. Refer to Carrier POWER System Design Manual part 3, Carrier E20-II software Refrigerant SUPPLY...
  • Page 18 3. All wiring must comply with applicable local and national codes. 4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual part 3, Carrier E20-II software Refrigerant Piping program, or appropriate ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers) hand- book for details on proper piping sizes and design.
  • Page 19: Step 3 - Complete Refrigerant Piping

    Step 3 — Complete Refrigerant Piping Units are shipped standard with fan cycle pressure switches for use with R-410A refrigerant. Carrier 30HXA units are shipped with fan cycles pressure switches for use with R-134a CAUTION condensing units. Do NOT bury refrigerant piping underground. Failure to Fan cycle pressure switches are to be installed on the dis- comply could result in equipment damage.
  • Page 20 MOTORMASTER PRESSURE TRANSDUCER MOTORMASTER LOCATION PRESSURE CIRCUIT B FAN CYCLE a09-592 TRANSDUCER PRESSURE LOCATION SWITCH CIRCUIT A LOCATIONS Fig. 14 — Unit Piping — Sizes 035-060 MOTORMASTER PRESSURE a09-593 TRANSDUCER MOTORMASTER LOCATION PRESSURE CIRCUIT B FAN CYCLE TRANSDUCER PRESSURE LOCATION SWITCH CIRCUIT A INSTALLATION...
  • Page 21: Refrigerant Line Sizing

    See Liquid Lift section for more information. Con- sult Carrier System Design Manual, Part 3, or Carrier E20-II Refrigerant Piping Computer Program for proper piping sizes and design.
  • Page 22 Table 7 — Available Liquid Lift (ft)* — English REFRIGERANT R-410A R-134a UNIT Temperature Difference (F)† 09DPS018 09DPS020 09DPS030 09DPM035 09DPM040 09DPM050 09DPM060 09DPM065 09DPM075 09DPM085 09DPM095 09DPM115 09DPM130 *Allows 7 psi drop for liquid line accessories with maximum charge. NOTES: †Saturated Condensing Temperature (entering) –...
  • Page 23: Step 4 - Make Electrical Connections

    Carrier warranty. operating temperature. All wiring must be in accordance with local or NEC regulations.
  • Page 24 a09-581...
  • Page 25 Table 9 — 09DP Electrical Data — Standard Fan SUPPLY VOLTAGE CONDENSER FAN 09DP UNIT SIZE V-Ph-Hz MOCP TOTAL QTY 208/230-3-60 380-3-60 460-3-60 575-3-60 380/415-3-50 208/230-3-60 14.9 380-3-60 460-3-60 575-3-60 380/415-3-50 208/230-3-60 14.9 380-3-60 460-3-60 575-3-60 380/415-3-50 208/230-3-60 14.9 380-3-60 460-3-60 575-3-60 380/415-3-50...
  • Page 26 Table 9 — 09DP Electrical Data — Standard Fan (cont) SUPPLY VOLTAGE CONDENSER FAN 09DP UNIT SIZE V-Ph-Hz MOCP TOTAL QTY 208/230-3-60 28.1 380-3-60 16.6 460-3-60 14.0 575-3-60 11.1 380/415-3-50 14.0 208/230-3-60 34.7 380-3-60 20.5 460-3-60 17.3 575-3-60 13.7 380/415-3-50 17.3 208/230-3-60 41.3...
  • Page 27 Table 10 — 09DP Electrical Data — Low Sound Fan SUPPLY VOLTAGE CONDENSER FAN 09DP UNIT SIZE V-Ph-Hz MOCP TOTAL QTY 208/230-3-60 380-3-60 460-3-60 575-3-60 380/415-3-50 208/230-3-60 13.5 380-3-60 460-3-60 575-3-60 380/415-3-50 208/230-3-60 13.5 380-3-60 460-3-60 575-3-60 380/415-3-50 208/230-3-60 13.5 380-3-60 460-3-60 575-3-60...
  • Page 28 Table 10 — 09DP Electrical Data — Low Sound Fan (cont) SUPPLY VOLTAGE CONDENSER FAN 09DP UNIT SIZE V-Ph-Hz MOCP TOTAL QTY 208/230-3-60 25.5 380-3-60 16.6 460-3-60 12.3 575-3-60 10.2 380/415-3-50 12.3 208/230-3-60 31.5 380-3-60 20.5 460-3-60 15.2 575-3-60 12.6 380/415-3-50 15.2 208/230-3-60...
  • Page 29: Control Circuit Wiring

    CONTROL CIRCUIT WIRING 09DP018-030 Units — The units require a 24-volt externally supplied power to energize the control circuit connected to TB2 terminal 1 and 2 shown in Fig. 20. 09DP035-0130 Units — Size 035 to 130 units are designed to operate with a 24-v field-supplied control power or can be powered by internal control transformer using contact closures to energize each control circuit.
  • Page 30: Step 5 - Check Condenser Fans

    a09-602 MAIN CONTROL FCPS AND POWER WIRING MOTORMASTER WIRING TRANSDUCER WIRING 09DP018-060 UNITS Fig. 26 — Fan Cycle Pressure Switch Wiring CONTROL MAIN FCPS AND WIRING POWER MOTORMASTER 09DP075-095 Units WIRING TRANSDUCER WIRING 09DP065-130 UNITS a09-600 a09-603 Fig. 24 — Control Box Entry Points a09-601 Fig.
  • Page 31: Step 6 - Configure Optional Motormaster

    positioned such that it is securely seated on this step. Tighten 2. The units are shipped with a package required for modifying the unit for single circuit application. The the bolt to 15 ± 1 ft-lb (20 ± 1.3 N·m). package is located in the bottom of the control box IMPORTANT: Check for proper fan rotation (counter- below the Motormaster controllers.
  • Page 32 It is strongly recommended that the user NOT change any to change setting. Press Mode to store new setting. programming without consulting Carrier service personnel. Unit damage may occur from improper programming. Pressing the Mode will store the new setting and also exit the PROGRAM mode.
  • Page 33 MANUAL RESET — If the fault condition has been re- • P52: DC BUS VOLTAGE - This displays the DC bus moved, cycle power to the Motormaster to reset the drive. voltage in percent of nominal. It is usually rated input voltage x 1.4.
  • Page 34: Step 7 - Install Accessories

    MODE CODE DESCRIPTION Line Voltage: 01 = low line, 02 = high line Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03=8 kHz Startup mode: flying restart Stop mode: coast to stop Standard Speed source: 01= keypad, 04=4-20mA (NO PI), 05= R410A, 06=R134a...
  • Page 35 Table 14 — Minimum Outdoor-Air Operating Temperature — English MINIMUM AMBIENT (F) WITHOUT MOTORMASTER CONTROL UNIT 09DP 100% Capacity 75% Capacity 50% Capacity 25% Capacity LEGEND — Temperature Difference (F) NOTES: 1. Based on 80 F condensing temperature at 100% and 75% capacity and a 75 F condensing temperature at 50% and 25% capacity.
  • Page 36 Table 15 — Minimum Outdoor-Air Operating Temperature — SI MINIMUM AMBIENT (C) WITHOUT MOTORMASTER CONTROL UNIT 09DP 100% Capacity 75% Capacity 50% Capacity 25% Capacity 16.6 14.2 16.7 16.6 17.6 13.9 16.9 19.1 18.2 18.7 11.1 19.7 21.3 20.1 20.1 16.6 10.6 12.3...
  • Page 37: Start-Up

    START-UP Due to the compact design of microchannel heat exchang- ers, refrigerant charge is reduced significantly. As a result, System Evacuation and Dehydration — Refer to charging procedures for MCHX units require very accurate GTAC II (General Training Air Conditioning), Module 4, “De- measurement techniques.
  • Page 38 ® Table 17 — Fan Control without Motormaster V Control 09DP FCPSA FCPSB UNIT SIZE OFM1 — — — — — — — — 020-030 OFM1 — — OFM2 — — — — OFM3 OFM3 OFM1 — — — — OFM3 OFM3 OFM1...
  • Page 39: Maintenance

    MAINTENANCE removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should Recommended Maintenance Schedule — The fol- be taken to clean MCHX condenser coils: lowing are only recommended guidelines. Jobsite conditions 1.
  • Page 40 Copyright 2011 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53090013-01 Printed in U.S.A. Form 09DP-3SI Pg 40 9-11 Replaces: 09DP-1SI...

Table of Contents