Gas Conversion; Warnings; Operations And Gas Setting - Biasi M300V.2025 SM User Manual And Installation Instructions

Combi
Table of Contents

Advertisement

9

GAS CONVERSION

9.1

Warnings

The commissioning of this boiler and
system must only be undertaken by a
Gas Safe Registered Engineer, quali-
fied to work on Liquefied Petroleum Gas
(LPG) in accordance with the require-
ments of the Gas Safe Installation and
Use Regulations.
Components used to adapt it to the type
of gas available must be genuine parts
only.
Factory setting = Natural gas.
9.2

Operations and gas setting

Check that the gas cock mount-
ed on the gas piping to the boil-
er is closed and that the appli-
ance is not powered.
• Enter "programming mode" by pressing
the 13 and 15 keys simultaneously for 5
seconds (Fig. 9.1) until HiS (Boiler Histo-
ry) appears on the LCD display (Fig. 9.2).
12
13
Fig. 9.1
Fig. 9.2
- 74 -
GAS CONVERSION
17
16
15
14
• Scroll through the various menus by
pressing the keys 13 (back) or 15 (for-
ward), until PAr (Parameters menu) ap-
pears on the LCD display (Fig. 9.3).
• Press the 14 key for 1 second to enter the
selected menu.
Fig. 9.3
• Scroll through the various parameters by
pressing the keys 13 (back) or 15 (for-
ward), until P02, which alternates with the
parameter value, appears on the LCD dis-
play (Fig. 9.4).
Fig. 9.4
• Press the 14 key for 1 second (Fig. 9.1) to
enter the selected parameter. The display
will show the following (Fig. 9.5).