Wall hung, fan flue, room sealed, high efficiency gas boiler User manual and Installation instructions RIVA COMPACT HE Models M96.24SM/C2 M96.28SM/C2 M96.32SM/C2...
Congratulations on your choice. RIVA COMPACT HE are condensing high efficiency sealed chamber fan flue gas boilers. They are fully electronically controlled and have electronic ignition. The materials they are made of and the control systems they are equipped with give you safety, a high level of comfort and energy savings to allow you to get the greatest benefit out of independent heating.
Page 3
Thermostat / Temperature gauge Biasi products are manufactured in accordance Description --- Sealed phial and capillary contain- with ISO 9000 and do not, and will not, contain any ing liquid.
You are strongly advised to flush out the instruction manuals thoroughly and then if system both cold and hot in order to remove necessary contact Biasi UK for advice and system and installation debris. assistance. Please remember that if you are in any doubt about the installation of this product you can contact our...
Appliance description Operation lights Three lights (10 in Fig. 1.3) give detailed indication Lamp OFF regarding the operation of the boiler. The following table gives the relationship between Lamp ON each of the possible light combinations and their meaning. Flashing lamp, alone or simultaneously with an other lamp.
INSTRUCTIONS FOR USE Warnings Refilling procedure 1 Isolate the boiler from the electrical supply at Biasi UK Ltd support the Benchmark initiat- the fused spur. Reconnect the filling loop as ive. The Benchmark Log Book is located at demonstrated in Fig. 2.1.
Instructions for use Ignition 1 Check that the valves located in the lower part of the boiler are open (Fig. 2.3). Fig. 2.5 C.h. circuit temperature Open position The output temperature of c.h. water is adjustable Fig. 2.3 from a minimum of about 38°C to a maximum of about 85°C (Fig.
Instructions for use Minimum Minimum Maximum Maximum Fig. 2.8 Fig. 2.6 Adjustment of the d.h.w. temperature is complete- ly separate from that of the c.h. circuit. Adjustment The adjustment system integrated within the In order to achieve optimal settings for economy boiler automatically controls the flow of gas to the and comfort, we recommend adjusting the oper- burner in order to keep the temperature of d.h.w.
Instructions for use Fig. 2.9 In these cases, however, it is advisable to install a small water treatment device or softener. With such a device you should avoid periodic descal- Closed position ing. Fig. 2.11 Consequently, the d.h.w. heat exchanger will keep its performance consistent for a longer period of time with resulting gas savings.
Page 12
Instructions for use H ON--- OFF display Setting the current time Note: with a new unit or when the reset button B has been pressed and the selector switch A is to position, the time display G is flashing. Fig. 2.15 Set the mode selector switch A to the position Activating the timed settings...
Page 13
Instructions for use To delete a time set press the button D or E until the The time delay can be set within the following symbols shown in Fig. 2.14 appears in the time ranges: display G. 1 to 23 hours with steps of 1 hour The new settings are memorized by moving the 1 to 27 days with steps of 1 day switch A to a different position.
USEFUL ADVICE Central heating cleaning by an Authorised Service Centre En- gineer, at least once a year. For reasonably economical service install a room During the service, the most important compo- thermostat. nents of the boiler will be inspected and cleaned. Never shut off the radiator in the area where the This service can be part of a maintenance con- room thermostat is installed.
Page 15
Useful advice ary to repeat the resetting operation several times some of the water in the appliance through the so as to remove the air present in the pipework. bleed valves present in the radiators. Safety lock--- out may occour even in case of an If in time, a reduction in domestic hot water blockage of the condensate drainage (e.g.
Technical information Hydraulic specifications The height difference between the pressure relief valve and the highest point in the system may be 7m at most. kPa bar For greater differences, increase the pre--- load pressure in the expansion vessel (44 on page 12) and the system, when cold, by 0.1 bar for each additional 1m.
GENERAL REQUIREMENTS Biasi UK Ltd support the Benchmark initiative. For Ireland (IE), reference should be made to the The Benchmark Log Book is located at the back current edition of I.S.813.2002 and the current of this manual and should be completed by the ETCI rules for electrical installations.
General requirements The minimum acceptable spacing from the ter- available both to the boiler and the other minal to obstructions and ventilation openings are appliance when they are in use at the same time. specified in Fig. 5.1. Pipework must be of adequate size. Pipes of a smaller size than the boiler inlet connection should not be used.
General requirements --- the drainpipe should be adequately fixed to The by --- pass is calibrated to assure a minimum pevent pipe sagging. flow of 500--- 600 lts/hr through the main heat ex- changer. If a part of the drainpipe runs externally this part should be kept as short as possible and protected If you are installing a system that includes thermo- to reduce the risk of freezing.
General requirements The correct method is shown in Fig. 5.3. is fully removed in order to ensure the efficiency of the new appliance is maintained. The temporary connection must be removed Details on flushing procedure are given in the sec- immediately after filling.
INSTALLATION Warnings The use of gas appliances is subject to statutory control; it is essential to observe the current regulations and laws in force (see also chapter 5). The appliance must discharge combustion products directly outside or into a suitable ex- haust duct designed for this purpose.
Installation Fig. 6.5 Choice of flue The following flue kits are available for connecting to the boiler: Standard horizontal flue kit (Fig. 6.6A) Co--- axial 60/100mm --- nominal length 1m Fig. 6.4 This kit is normally supplied with the boiler and can be fitted to allow discharge to the rear or either Fitting the flue system side of the boiler via the flanged boiler adapter...
Page 32
Installation Co--- axial 60/100mm. Elbow kits enable the standard flue kits to be offset to overcome obstructions or ensure the correct clearances for the flue terminal. Each elbow used in addition to the standard flanged elbow reduces 90û=--- 1,65 m the overall acceptable length of the flue system as follows: 45û...
Installation For M96.32SM/... Equivalent length Restrictor (air duct + flue duct) Between 1 and 24 m ø 50 mm Tab. 6.2 Vertical--- roof kit (Fig. 6.9) This kit allows vertical termination of the flue pipe through the roof. The kit is 1.2 m in length. Exten- sion pieces (Co--- axial) are also available which al- lows the flue system to be extended to a total overall maximum permissible length.
Installation 8 Connect the room thermostat between ter- minals 1 and 3 as shown in Fig. 6.14. Do not connect live wires to terminals to which the room thermostat must be con- nected. Power supply Room thermostat terminal block Fig. 6.12 External controls terminal block For the electrical connection to the boiler use elec-...
COMMISSIONING WARNING The commissioning of this boiler and system must only be undertaken by a professionally qualified person in accordance with the re- quirements of the Gas Safety Installation and Regulations approved C.O.R.G.I. Ensure that the Benchmark Log Book is satis- factorily completed during the commissioning process.
Commissioning Lighting the boiler 6 Purge the air from the pump by unscrewing the pump plug 21 (Fig. 7.2); release the pump Some products incorporate an anti cycling time shaft by turning in the direction indicated by delay. It is normal when first switching the boiler on the arrow on the information plate.
Commissioning lowed to ensure maximum operating efficiency at the burner), accordingly with the model of from the boiler. boiler installed. 1 Remove the front panel of the case (see sec- 11 Switch off the boiler and re--- connect the elec- tion 9.2 in this manual).
Commissioning lector 8 to the OFF position and then back to that indicated in Fig. 7.5. 5 Repeat this process two to three times leaving 30 second intervals between each ignition. Check the ignition pressures and visually check that the burner lights uniformly and in a controlled manner.
Page 40
Commissioning 10 Turn the boiler OFF and ON positioning the Natural (G20) function selector 8 as indicated in Fig. 7.9 Fig. 7.9 1 2 3 4 5 6 7 8 9 10 11 12 13 11 Keep pressed the reset button 7 for about 10 seconds until the lock--- out signal lamp 6 M96.24SM/...
Commissioning 7.12 Checking the condensate Propane (G31) drain pipe Check the soundness and integrity of the conden- sate drain pipe. Verify the cleanness and correct filling of the con- densate traps. 7.13 Instructing the user Hand over this combined User & Installation man- ual and the Service manual to the end user and ex- plain how to use the unit in both c.h.
Page 42
GAS CONVERSION Warnings The commissioning of this boiler and sys- tem must only be undertaken by a pro- fessionally qualified person in accordance with the requirements of the Gas Safety In- stallation and Use Regulations and be ap- proved by C.O.R.G.I. Components used to adapt it to the type of gas available must be genuine parts only.
Page 43
Gas conversion 16 To reset the boiler to the normal operation turn Position of Approx. Max current it ON by the function selector 8 on the desired supply knob 9 through the modulator operation and checking the ignition pressure device and that the burner lights up uniformly.
MAINTENANCE Warnings Side panels 3 Loosen the screws B. Bring the bottom of the The procedures detailed in this chapter must panels away from the boiler and lift them, free- be carried out only by a professionally ing them from the top hooks (Fig. 9.2). qualified person.
Maintenance boiler is being drained to prevent freezing, the If the pressure is lower, take steps to correct the d.h.w. heat exchanger must be removed and pressure level. inverted to drain fully or an antifreeze solution added. Cleaning the burner The sloping and multi--- gas type burner (29 on page 12) does not need special maintenance, but it is sufficient to dust it with a bristle paintbrush.
Page 48
*1796211641* 17962.1164.1 4206 48A5 UK Biasi UK Ltd Newman Park, Western Way Wednesbury, WS10 7BJ Sales Tel No: 0121 506 1340 Sales Fax No: 0121 506 1360 Service Tel No: 0121 506 1350 Service Fax No: 0121 506 1370 www.biasi.co.uk...