Service Valves; Open The Service Valves - Bosch IDS BOVA15 Installation Instructions Manual

Split system heat pump
Table of Contents

Advertisement

Installation Instructions

10 Service Valves

10.1 Open the Service Valves

WARNING: MODERATE TO SEVERE BURNS
Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn counterclockwise until
the valve stem just touches the rolled edge. No torque is
required. Failure to follow this warning will result in abrupt
release of system charge and may result in personal injury
and /or property damage.
      Leak check and evacuation must be completed before opening the
service valves. The brazed lineset valves should be used for leak
checking and vacuuming. Using the separate suction port for this
process will result in loss of charge.
The Suction Service Valve must be opened fi rst BEFORE opening the
Liquid Service Valve.
1.
Remove Service Valve Cap (Fig. 23).
2.
Fully insert hex wrench into the stem and back out counterclockwise until
valve stem just touches the rolled edge (approximately five (5) turns.)
3.
Replace the Valve Stem Cap to prevent leaks. Tighten finger tight plus an
additional 1/6 turn.
4.
Repeat STEPS 1 - 3 for Liquid Service Valve.
1 4 |
Cap
Unit Side
of Service
Valve
Service Port
Figure 23
Bosch IDS BOVA15 Split System Heat Pump - BTC 761701317 A (02.2022)
5/16" Hex Wrench
for Suction Service Valve
3/16" Hex Wrench
for Liquid Service Valve
Rolled Edge to
Captivate Stem
Hex Headed
Valve System

Hide quick links: