Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean
that the system is not properly charged or that a problem exists with some component in the system.
IMPORTANT
Model
−024
°F (°C)**
Liquid
65 (18.3)
234
70 (21.1)
249
75 (23.9)
268
80 (26.7)
289
85 (29.4)
310
90 (32.2)
334
95 (35.0)
358
100 (37.8)
383
105 (40.6)
408
110 (43.3)
436
115 (46.1)
465
*
Typical pressures only, expressed in psig (liquid +/− 10 and vapor+/− 5 psig); indoor match up, indoor air quality, and indoor load will cause the pressures
to vary. These operating pressures are also listed on the unit charging sticker (580005−01) located on the access panel.
** Temperature of air entering outdoor coil.
°F
Psig
°F
32
100.8
48
33
102.9
49
34
105.0
50
35
107.1
51
36
109.2
52
37
111.4
53
38
113.6
54
39
115.8
55
40
118.0
56
41
120.3
57
42
122.6
58
43
125.0
59
44
127.3
60
45
129.7
61
46
132.2
62
47
134.6
506510−01
Downloaded from
ManualsNet.com
Table 4. Normal Operating Pressures (Liquid +10 and Suction +5 psig)*
Use this table to perform maintenance checks; it is not a procedure for charging the
system. Minor variations in these pressures may be due to differences in installations.
Significant deviations could mean that the system is not properly charged or that a