Electrical

Electrical Connections

WARNING
1. Electrical connection shall be made only by authorized electricians and in accordance with
local electrical requirements and codes.
2. The system must be grounded.
3. Single phase models and three phase models are available; for each of them, the
necessary wiring diagram is shown.
4. Connect the unit to the main power supply as per its applicable wiring diagram.
5. Use supply wire sizes as per local electrical codes and regulations.
O
U
C
UTDOOR
NIT
ONNECTIONS
Mains Installation
1. Install a dedicated circuit from the mains switch
board. Circuit breaker requirements as per table
below.
2. Connect the mains cables to the incoming
connection block on the outdoor unit
Use supply wire sizes as per local electrical
codes and regulations.
Recommended
Model
Circuit Breaker
B009RS
B012RS
B015RS
B016RT
B019RT
PLEASE NOTE: Circuit breaker and cable sizes are subject to cable run length – refer
AS 3000 wiring rules
3. Connect 1.0mm twin active cable between the
ducted gas central heater and the outdoor unit.
This is for 24Volt switched voltage from the gas
central heater to activate the refrigerative system.
See wiring diagrams on the next pages for
outdoor unit connections and the central heater
instructions for the heater control connections.
Installation Instructions
C
C
OOLING
OMPONENT
Full Load
Amps
32A
16.5
32A
21.8
40A
32.4
3 x 32 A
14.8
3 x 32 A
19.5
Recommended
Cable Size
4.0mm
4.0mm
6.0mm
4.0mm
4.0mm
Page 19