BONAIRE B009RS Installation Manual
Hide thumbs Also See for B009RS:

Advertisement

Installation Manual
D
C
UAL
YCLE
R
C
C
EFRIGERATED
OOLING
OMPONENT
B009RS/DC
B012RS/DC, B015RS/DC
B016RT/DC, B019RT/DC

Advertisement

Table of Contents
loading

Summary of Contents for BONAIRE B009RS

  • Page 1 Installation Manual YCLE EFRIGERATED OOLING OMPONENT B009RS/DC B012RS/DC, B015RS/DC B016RT/DC, B019RT/DC...
  • Page 3: Table Of Contents

    YCLE EFRIGERATED OOLING OMPONENT Table of Contents General ............................4 Product Selection Matrix ....................... 4 UNIT DETAILS ..........................5 Outdoor Unit Dimensions ......................5 Outdoor Unit Access and Clearances ................... 6 Indoor Unit Dimensions ......................... 7 Indoor Coil Clearances........................8 UNIT INSTALLATION ........................
  • Page 4: General

    The heater provides the controls and fan for the heating and cooling system. The Bonaire Dual Cycle cooling component includes two separate units – indoor coil and outdoor Unit. The two components are interconnected by two refrigerant tubes and an electric cable.
  • Page 5: Unit Details

    YCLE EFRIGERATED OOLING OMPONENT Dimensions & Clearances Unit Details UTDOOR IMENSIONS B009RS B012RS B015RS B016RT B019RT Unit Weight B009RS 92kg B012RS 97kg B015RS 103kg 1260 Connections Inside Unit B016RT 108kg 1260 Connections Inside Unit B019RT 131kg 1465 Page 5 Installation Instructions...
  • Page 6: Outdoor Unit Access And Clearances

    YCLE EFRIGERATED OOLING OMPONENT Dimensions & Clearances UTDOOR CCESS AND LEARANCES When the back is close to the Wall In selecting a proper location, the following criteria The top and the front need to be open. This includes protruding window sills. must be considered: The outdoor unit and the indoor unit must be installed as close to each other as possible, within...
  • Page 7: Indoor Unit Dimensions

    YCLE EFRIGERATED OOLING OMPONENT Dimensions & Clearances NDOOR IMENSIONS Unit Dimensions Unit Weight B009DC 15Kg B012DC 20Kg B015DC 20Kg B016DC 20Kg B019DC 24.5Kg Page 7 Installation Instructions...
  • Page 8: Indoor Coil Clearances

    YCLE EFRIGERATED OOLING OMPONENT Dimensions & Clearances NDOOR LEARANCES Clearance Options for Maintenance Unit B009HD B012HD B015HD B016HD B019HD Page 8 Installation Instructions...
  • Page 9: Unit Installation

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation Unit installation NDOOR Coil Location The indoor coil is designed for installation in conjunction with a duct gas central heater within a ceiling/roof space or other compartment, where there is no influence from outdoor conditions. While selecting the location, the following conditions must be assured: a) The location should assure free flow of the...
  • Page 10: Coil - Floor Or Platform Mounting

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation Coil - Floor or Platform Mounting 1. Create a platform using bearers and chipboard. Place the unit platform over load bearing walls or on strategically located trusses in the roof space. 2. Place serrated rubber pads or isolating springs under each corner of the unit to minimize / eliminate any noise transmission.
  • Page 11: Outdoor Unit

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation UTDOOR Page 11 Installation Instructions...
  • Page 12: Condenser Installation

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation ONDENSER NSTALLATION Installation on flat surface (roof, ground, etc) Install outdoor unit support in a position elevated at least 100 mm on a concrete pad, concrete block or wooden beams, in order to allow free water flow underneath.
  • Page 13: Installation Notes

    TUBING LENGTH, UP TO – (IN METRES, ONE WAY) MAXIMUM MAXIMUM MODEL LINE TUBING HEIGHT LENGTH DIFFERENCE 19.05MM (¾”) 19.05MM (¾”) 19.05MM (¾”) 22.23mm (⅞”) B009RS Liquid 9.58mm (⅜”) 9.58mm (⅜”)” 9.58mm (⅜”) 9.58mm (⅜”) 19.05MM (¾”) 19.05MM (¾”) 22.23mm (⅞”) 22.23mm (⅞”) B012RS Liquid 9.58mm (⅜”) 9.58mm (⅜”)”...
  • Page 14: Recommendation For Interconnection Tubing Installation

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation Recommendation for Interconnection Tubing Installation Three possible versions are schematically illustrated: 1) The outdoor unit installed above the indoor unit – such installation requires an oil trap in the gas line at the lowest point of the riser. The radius of the oil trap should be as short as possible.
  • Page 15: Pipe Installation

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation NSTALLATION WARNING This paragraph describes the necessary steps for setting the unit into operation. Be sure to follow the instructions, to assure proper functioning of the air conditioner. The outdoor unit is pre-charged with the correct amount of refrigerant. In extended runs, for additional refrigerant charge please refer to the outdoor unit name plate.
  • Page 16: Connecting The Tubes

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation 2. Before brazing wrap a wet cloth around pipes next to the indoor unit to prevent hot pipes from melting foam insulation in the unit. Make sure the flame or heat from the flame does not contact the unit casing or wiring, or damage will occur 3.
  • Page 17: Evacuation And Setting In Operation

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation VACUATION AND SETTING IN OPERATION a) Connect two charging hoses from the charging set to the outdoor unit as shown in the diagram below. b) Connect the centre hose of the charging set to a vacuum pump. c) CAUTION - turn on the vacuum pump and make sure that the low pressure gauge reading moves from 0 kPa to -100 kPa;...
  • Page 18: Additional Charge

    YCLE EFRIGERATED OOLING OMPONENT Unit Installation DDITIONAL HARGE 1. Each condenser unit is supplied pre-charged for 10 meters of 9.53 (3/8”) liquid line. For additional charge add 57 grams per meter for over and above the specified system pre-charged length. See the unit name plate for this information. DO NOT exceed the maximum equivalent pipe length on each unit.
  • Page 19: Electrical Connections

    Use supply wire sizes as per local electrical codes and regulations. Recommended Full Load Recommended Model Circuit Breaker Amps Cable Size B009RS 16.5 4.0mm B012RS 21.8 4.0mm B015RS 32.4 6.0mm B016RT 3 x 32 A 14.8...
  • Page 20: Wiring Diagram - Single Phase Outdoor Unit

    YCLE EFRIGERATED OOLING OMPONENT Electrical IRING IAGRAM INGLE HASE UTDOOR Dual Cycle Connection Page 20 Installation Instructions...
  • Page 21: Wiring Diagram - 3 Phase Outdoor Unit

    YCLE EFRIGERATED OOLING OMPONENT Electrical - 3 P IRING IAGRAM HASE UTDOOR Dual Cycle Connection Page 21 Installation Instructions...
  • Page 22: Commissioning

    YCLE EFRIGERATED OOLING OMPONENT Commissioning Commissioning OMMISSIONING HECK Site □ Return panels and covers to their correct position and check that they are well secured. □ Ensure all service caps are fitted and correctly tightened. □ Attach the electrical wires and pipes to the wall with clamps. □...
  • Page 24 Manufactured by Climate Technologies ABN 13 001 418 042 26 Nylex Avenue Salisbury, SA 5108 Australia www.climatetechnologies.com.au 6602212/A...