4. INSTALLATION AND PRE-OPERATION SETTING PROCEDURE

4.2.2 Installation environment

CAUTION
(2) When using the DIN rail adapter, note the following in mounting the DIN rail.
(a) Applicable DIN rail type (conforming to JIS C2812)
TH35-7.5Fe
TH35-7.5Al
(b) DIN rail mounting screw pitch
When mounting the DIN rail, tighten screws in 200mm(7.88inch) or less pitch.
When installing the module, avoid the following environment. If the environment of
the module used is outside the range of general specifications, an electric shock,
fire, misoperation or product damage or deterioration can occur
 Ambient temperature outside the range 0 to 55°C
 Ambient humidity outside the range 10 to 90%RH
 Condensation due to sudden temperature changes
 Corrosive or combustible gasses
 Dust, conductive powder (e.g. metal filings), oil mist, salt and organic solvent
 Direct sunlight
 Strong power and magnetic fields
 Vibration and impact
4 - 3