Configurable 'Gpi' Input; Purge' Relay Output For Blowing Out (With Fda241 Only) - Siemens FDA241 Mounting & Installation

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Installation
4

Configurable 'GPI' input

4.3
4.4
26
Building Technologies
Fire Safety
Configurable 'GPI' input
Configurable input for an external switch. The setting is made in the 'Relay and
GPI' menu with the 'FXS2051 ASD Configuration Tool' software.
Monitoring for open line
Monitoring for short circuit and open line
Properties
Can be configured to trigger the following actions:
Switching to Manned/Unmanned (not possible when fire control panel
FC20xx/FC72x is connected)
Resetting
Activating blowing-out unit
Deactivates all relays and alarm outputs
Monitoring for open line (1 resistor)
Monitoring for short circuit and open line (2 resistors)
Input for error monitoring on the external power unit
'Purge' relay output for blowing out
(with FDA241 only)
Relay output for controlling an external blowing-out unit.
Connection: n.o.
Properties
Suitable for controlling an external blowing-out unit.
Configuration of:
Purge interval
Purge duration
When the aspirating smoke detector is in operation, the setting is made on the
FDnet/C-NET using the fire control panel configuration software.
For fire control panels FC20xx: 'SintesoWorks'
For fire control panels FC72x: 'Cerberus-Engineering-Tool'
When the aspirating smoke detector is in standalone operation, the setting is made
in the 'Purge' menu with the 'FXS2051 ASD Configuration Tool' software.
firealarmresources.com
A6V10345654_h_en_--
2015-05-29