Model CC1 — 2.8 K-factor
Combustible Concealed Space Sprinklers
Specific Application, Upright
General
Description
The Model CC1 Combustible Con-
cealed Sprinklers are fast response,
upright, specific application sprinklers
designed to provide protection of light
hazard combustible, as well as non-
combustible, concealed spaces re-
quiring sprinkler protection. The CC1
Sprinklers comply with the criterion
for the protection of combustible con-
cealed spaces as described in NFPA
13.
The Model CC1 Sprinklers can in
some cases allow for the use of Blaze-
Master CPVC piping within concealed
spaces requiring automatic sprinkler
protection. At one time, the listing of
CPVC piping for fire protection sys-
tems did not allow the use of CPVC
piping
in
combustible
spaces requiring automatic sprin-
kler protection. With the extensive full
scale fire testing of the Model CC1
Combustible Concealed Space Sprin-
klers, performed at UL, BlazeMaster
CPVC may now be used in the speci-
fied combustible concealed spaces
requiring automatic sprinkler protec-
tion, when installed in accordance
with this technical data sheet.
The effectiveness of the Model CC1
Sprinklers, in the combustible con-
cealed
spaces
investigated,
clearly evident during the full scale fire
testing for this product. Concealed
spaces between floors, as well as low
pitch attics are inherently shallow.
Standard spray sprinklers, by design,
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently
damage
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
have an umbrella like spray pattern
that poses a difficult challenge when
trying to achieve effective coverage
within a shallow space. The Model
CC1 Combustible Concealed Space
Sprinklers have addressed this diffi-
cult fire challenge.
NOTICE
The Model CC1 Combustible Con-
cealed Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
concealed
dition. Contact the installing contrac-
tor or product manufacturer with any
questions
Sprinkler
Identification
Numbers (SINs)
TY1189 - Upright, 2.8K
TY1189 is a redesignation for C1189.
Technical
was
Data
Approvals
UL Listed.
(Listings and approvals only apply to
the service conditions indicated in the
Design Criteria sections.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT or ISO 7-R 3/4
a
sprin-
SEPTEMBER 2014
Worldwide
www.tyco-fire.com
Contacts
Discharge Coefficient
K = 2.8 gpm/psi1/2
(40,3 lpm/bar1/2)
Temperature Rating
175°F (79°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Button. . . . . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly. . . . . . . . . . . . .Stainless
Steel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . Glass (3 mm)
Compression Screw. . . . . . . . . . . . . Brass
Deflector. . . . . . . . . . . . . . . . . . . . . Bronze
TFP630

Advertisement

loading
Need help?

Need help?

Do you have a question about the CC1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Product CC1

  • Page 1 175°F (79°C) kler protection. With the extensive full questions Finish scale fire testing of the Model CC1 Sprinkler Natural Brass Combustible Concealed Space Sprin- klers, performed at UL, BlazeMaster Physical Characteristics...
  • Page 2: Operation

    3 to protect the BlazeMaster CPVC (Fig. 3). by the operation of the CC1 Sprinklers product. Minimum Distance Away from in the event of a fire. A minimum lateral distance of 18...
  • Page 3 OBSTRUCTION CEILING WHEN OFFSETTING CPVC PIPE OVER 6" (150 mm) MAXIMUM ABOVE CEILING OR AN OBSTRUCTION, A CC1 SPRINKLER NON-COMBUSTIBLE CEILING INSULATION, MUST BE INSTALLED DIRECTLY ON THE OR 1/3 THE DEPTH OF CONCEALED SPACE CPVC PIPE OVER THE OBSTRUCTION...
  • Page 4: Installation

    16 inches (400 mm) General Instructions bar joist construction (Fig.4) the depth The CC1 Sprinklers are to be installed • non-combustible insulation filled of the concealed space is 36 inches upright and with their frame arms (ref.
  • Page 5 UPPER 2x FLOOR SOLID INSTALLED PARALLEL WITH WOOD JOISTS, DECK WOOD JOISTS NOT NECESSARILY WITH PIPE RUN 54" (1372 mm) MAXIMUM CC1 SPRINKLER 6" (152 mm) 36" (914 mm) 2" (51 mm) MAXIMUM 1-1/2" (38 mm) MINIMUM CEILING CEILING FRAMING...
  • Page 6: Care And Maintenance

    Sprinklers dam- aged by dropping, striking, wrench WRENCH RECESS twist/slippage, or the like, must be The Model CC1 Sprinklers must be (USE END "B" FOR replaced. Also, replace any sprinkler maintained and serviced in accor- MODEL CC1)
  • Page 7 48" to <54" 14" Specify: TY1189, 2.8 K-factor, Model DISTANCE (FIG. 2) REQUIRED (1219,2 mm to <1371,6 mm) (355,6 mm) CC1, 175°F (79°C), Upright, Specific BY THE SPECIFIC APPLICATION 54" to <60" 16-1/2" Application, Combustible Concealed LISTING IS MAINTAINED. (1371,6 mm to <1524,0 mm)
  • Page 8 TFP630 Page 8 of 8 GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 Copyright © 2014 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation.