Model CC1 — 2.8 K-factor
Combustible Concealed Space Sprinklers
Specific Application, Upright
General
Description
The Model CC1 Combustible Con-
cealed Sprinklers are fast response,
upright, specific application sprinklers
designed to provide protection of light
hazard combustible, as well as non-
combustible, concealed spaces re-
quiring sprinkler protection. The CC1
Sprinklers comply with the criterion
for the protection of combustible con-
cealed spaces as described in NFPA
13.
The Model CC1 Sprinklers can in
some cases allow for the use of Blaze-
Master CPVC piping within concealed
spaces requiring automatic sprinkler
protection. At one time, the listing of
CPVC piping for fire protection sys-
tems did not allow the use of CPVC
piping
in
combustible
spaces requiring automatic sprin-
kler protection. With the extensive full
scale fire testing of the Model CC1
Combustible Concealed Space Sprin-
klers, performed at UL, BlazeMaster
CPVC may now be used in the speci-
fied combustible concealed spaces
requiring automatic sprinkler protec-
tion, when installed in accordance
with this technical data sheet.
The effectiveness of the Model CC1
Sprinklers, in the combustible con-
cealed
spaces
investigated,
clearly evident during the full scale fire
testing for this product. Concealed
spaces between floors, as well as low
pitch attics are inherently shallow.
Standard spray sprinklers, by design,
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently
damage
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
have an umbrella like spray pattern
that poses a difficult challenge when
trying to achieve effective coverage
within a shallow space. The Model
CC1 Combustible Concealed Space
Sprinklers have addressed this diffi-
cult fire challenge.
NOTICE
The Model CC1 Combustible Con-
cealed Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
concealed
dition. Contact the installing contrac-
tor or product manufacturer with any
questions
Sprinkler
Identification
Numbers (SINs)
TY1189 - Upright, 2.8K
TY1189 is a redesignation for C1189.
Technical
was
Data
Approvals
UL Listed.
(Listings and approvals only apply to
the service conditions indicated in the
Design Criteria sections.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT or ISO 7-R 3/4
a
sprin-
SEPTEMBER 2014
Worldwide
www.tyco-fire.com
Contacts
Discharge Coefficient
K = 2.8 gpm/psi1/2
(40,3 lpm/bar1/2)
Temperature Rating
175°F (79°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Button. . . . . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly. . . . . . . . . . . . .Stainless
Steel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . Glass (3 mm)
Compression Screw. . . . . . . . . . . . . Brass
Deflector. . . . . . . . . . . . . . . . . . . . . Bronze
TFP630