Tyco Fire Product CENTRAL DS-1 Instruction Manual

Tyco Fire Product CENTRAL DS-1 Instruction Manual

Dry type sprinklers quick and standard response, extended coverage

Advertisement

Quick Links

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series DS-1 — 5.6 K-factor
Dry Type Sprinklers
Quick and Standard Response, Extended Coverage
General
Description
The Series DS-1, 5.6 K-factor, Quick
Response (3 mm Bulb) and Standard
Response (5 mm Bulb), Extended
Coverage Horizontal Sidewall, Dry
Type Sprinklers are decorative glass
bulb automatic sprinklers. They are in-
tended for use in applications where
the sprinklers and/or a portion of the
connecting piping may be exposed to
freezing temperatures (e.g., horizontal
piping extensions through a wall to
protect an unheated area of a build-
ing). The Series DS-1 Extended Cov-
erage Horizontal Sidewall Sprinklers
are designed for extended coverage
use in light hazard occupancies
(ECLH).
WARNINGS
The Series DS-1 Dry Type Sprinklers
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
The Series DS-1 Dry Type Sprinklers
must only be installed in fittings that
meet the requirements of the Design
Criteria section.
Page 1 of 6
Model/Sprinkler
Identification
Numbers
TY3338 - (3 mm Bulb Type)
TY3358 - (5 mm Bulb Type)
Technical
Data
Approvals
UL and C-UL Listed. NYC Approved.
(Refer to Table A)
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connection
1 inch NPT
Discharge Coefficient
1/2
K = 5.6 GPM/psi
1/2
(80,6 LPM/bar
)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Natural Brass, Chrome
Plated, White Polyester
Escutcheon: White Coated or Chrome
Plated
Physical Characteristics
Inlet . . . . . . . . . . . . .
Plug . . . . . . . . . . . . .
Yoke . . . . . . . . . Stainless Steel
Casing . . . Galvanized Carbon Steel
Insert . . . . . . . . . . . . . Bronze
Bulb Seat . . . . . . Stainless Steel
Bulb . . . . . . . . . . . . . . Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . . Bronze
Frame . . . . . . . . . . . . . Bronze
Guide Tube . . . . . Stainless Steel
Water Tube . . . . . Stainless Steel
FEBRUARY, 2002
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
Spring . . . . . . . . Stainless Steel
Sealing Assembly . . . . . . . . . .
. . . . . . Beryllium Nickel w/Teflon*
Escutcheon . . . . . . Carbon Steel
Patents
U.S.A. Patent Number 5,188,185 may
be applicable to the Series DS-1, 5.6
K-factor, Quick and Standard Re-
sponse, Extended Coverage Horizon-
tal Sidewall, Dry Type Sprinklers

Operation

When the Series DS-1 is in service,
water is prevented from entering the
assembly by the Plug & Belleville Seal-
ing Assembly (Ref. Figure 1) in the
Inlet of the Sprinkler. The glass Bulb
contains a fluid that expands when ex-
posed to heat. When the rated tem-
perature is reached, the fluid expands
sufficiently to shatter the glass Bulb,
and the Bulb Seat is released. The
Copper
compressed Spring is then able to ex-
Copper
pand and push the Water Tube as well
as the Guide Tube outward. This action
simultaneously pulls inward on the
Yoke, withdrawing the Plug & Belleville
Seal from the Inlet allowing the sprin-
kler to activate and flow water.
* Registered Trademark of DuPont
TFP520
TFP520 (5-9.0)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CENTRAL DS-1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Product CENTRAL DS-1

  • Page 1 Customer Service/Sales: Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Series DS-1 — 5.6 K-factor Dry Type Sprinklers Quick and Standard Response, Extended Coverage General Model/Sprinkler Description Identification Numbers The Series DS-1, 5.6 K-factor, Quick Response (3 mm Bulb) and Standard Response (5 mm Bulb), Extended TY3338 - (3 mm Bulb Type)
  • Page 2 Page 2 of 6 TFP520 Design SPRINKLER FINISH Criteria TY3338 HSW (3 mm Bulb Type) The Series DS-1 Sprinklers are in- w/ Standard Escutcheon tended for use in fire sprinkler systems (Ref. Fig. 2) designed in accordance with the ex- tended coverage installation guide- TY3358 HSW lines provided by NFPA 13 and the...
  • Page 3 TFP520 Page 3 of 6 PLUG WITH YOKE CASING INSERT FRAME 3 or 5 mm DEFLECTOR GASKETED SPRING BULB PLATE SEAL WATER GUIDE BULB VENT COMPRESSION INLET 1" NPT SPRING TUBE TUBE SEAT HOLE SCREW FIGURE 1 TY3338 (3 mm BULB) AND TY3358 (5 mm BULB) EXTENDED COVERAGE HORIZONTAL SIDEWALL ASSEMBLY outlet of a Central Figure 730 Mechani- ORDER LENGTHS:...
  • Page 4 Page 4 of 6 TFP520 facturer should be contacted relative Installation Care and to any questions. Maintenance It is recommended that automatic The Series DS-1 Dry Type Sprinklers sprinkler systems be inspected, must be installed in accordance with tested, and maintained by a qualified the following instructions: The Series DS-1 Dry Type Sprinklers Inspection Service.
  • Page 5 TFP520 Page 5 of 6 • Temperature Rating. Ordering • Sprinkler Finish. Procedure • Standard Escutcheon and Finish. • Part Number fro Table C. Contact your local distributor for avail- ability, and please specify the follow- 2. W-Type 7 Sprinkler Wrench. ing: Refer to the Price List for complete 1.
  • Page 6 Page 6 of 6 TFP520 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446...

Table of Contents