Summary Table Of Advanced Programing Mode (Apm) Options - Danfoss HP8211-1RJ Installation Instructions Manual

Heat pump thermostats
Table of Contents

Advertisement

ADVANCED PROGRAMMING MODE (APM) OPTIONS SUMMARY
For further details of the APM options refer to pages 6, 7 & 8.
NOTE: If centigrade display has been selected then all temperatures will be the °C equivalent of the °F temperatures shown below.
Option
Description
1
Temperature override timer
2
Fan run-on timer after each cooling cycle
3
Fan run-on timer after each heating cycle
Enable or Disable occupancy relay and Smart
4
Fan programming
5
Fan Lock
6
Use of keyboard disable (DIP switch 5)
7
Minimum deadband
8
Max Heating Temp
9
Min Cooling Temp
A
Min Heating Temp
b
Max Cooling Temp
c
Optimum start control for heating
d
Optimum start control for cooling
E
Calibration
F
Compressor minimum off time
H
Compressor minimum on time
L
Low balance point (low temp cut off)
N
High balance point
r
Remote room sensor disable
Default Setting Optional Setting
NE (next timed
1, 2, 3, 4Hr, or
event will reset
DIS
the override)
30, 60 or 90
OFF
seconds
30, 60 or 90
OFF
seconds
DIS (able)
En (able)
ALL
LOC
NOR
FUL
5˚F
2˚F, 7˚F or 10˚F
86˚F
85˚F to 43˚F
61˚F
62˚F to 104˚F
43˚F
44˚F to 86˚F
104˚F
103˚F to 61˚F
0 (off)
1-8
0 (off)
1-8
0˚F
+ 3˚F to -3˚F
4 mins
3 mins or 2 mins Sets the compressor min Off time for each cycle
2 mins
0-4 mins
-22˚F to +60˚F or
16˚F
Off
50˚F
32˚F to 70˚F or Off
En (able)
DIS (able)
Comments
1, 2, 3 or 4 hours override, or override disabled
Fan runs on for additional 30, 60 or 90 seconds after
each cooling cycle
Fan runs on for additional 30, 60 or 90 seconds after
each heating cycle
When enabled this feature sets 3 functions:
1. Occupancy relay can be set to open or close at
each event time
2. The fan can be set for AUTO or ON at each event
time.
3. Optimum Start Control will be effective at each
Occupied Event time.
When this feature is disabled the Occupancy Relay
and smart fan energizes at first programed event
time and de-energizes at the last programed event
time, and OSC will only operate at the first event time
of the day.
ALL allows AUTO, ON or SMART fan to be selected.
LOC disables the fan button and locks the
thermostat in SMART fan mode.
NOR = PROG key disabled and temperature override
limited to 3˚F up or down from setpoint. This feature
may be used in conjunction with options 1 & 5. FUL
= full keyboard lockout.
Minimum temperature difference between heating
and cooling setpoints
Used in conjunction with Option A
Used in conjunction with Option b
Used in conjunction with Option 8
Used in conjunction with Option 9
Sets the maximum amount of start up time for
heating. 1 = 15 mins, 2 = 30 mins up to 8 =
120mins. Refer to table on page 7
See Option c above
Raises or lowers display temp in 1˚F steps
Sets the compressor min On time for each cycle
Below this temp the thermostat switches off the heat
pump and runs with auxiliary heat alone. Only
available when outdoor sensor is installed
Above this temp the thermostat switches off the
auxiliary heat and runs with the heat pump alone.
Only available when outdoor sensor is installed
Disables or enables the remote room sensor. Only
available when remote sensor is installed
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hp8321-1rj

Table of Contents