Operation
2.1

Unpacking

Upon receipt of your device, verify the appropriate purchase order.
NOTICE
Store the device in a suitable container to prevent possible damage during handling.
2.2

Operate

Prerequisites
WARNING
Hazardous areas
Do not open this device for any reason in a hazardous area.
WARNING
Explosion
Do not open when an explosive atmosphere is present.
Only use replaceable battery pack Rosemount 00975-0900-0012.
NOTICE
Disconnect external devices, such as fire alarms and automatic extinguishing systems,
before performing maintenance.
Procedure
1. Verify that you are using the correct simulator that fits the tested detector per
2. Verify that you are at the correct distance from the detector according to the type
3. Aim the flame simulator using the mechanical sight at the center of the detector.
Once the trigger is pressed, with an initial two second delay, the equipment will operate
for a maximum of 60 seconds, following which the equipment cannot be operated for a
minimum period of 30 seconds.
Rosemount FS-UVIR-975
1-1.
of detector and the detector sensitivity.
See
Table
6-1.
Push the Activate button and then use the halogen beam for fine adjustment
towards the center of the detector.
Operation
May 2022