Summary of Contents for Emerson Rosemount FS-UVIR-975

  • Page 1 Reference Manual 00809-0800-4975, Rev DD May 2022 ™ Rosemount FS-UVIR-975...
  • Page 2 Emerson does not assume any liability arising out of the application or any use of any product or circuit described herein;...
  • Page 3 Warranty 1. Limited Warranty . Subject to the limitations contained in Section 2 (Limitation of Remedy and Liability) herein, Seller warrants that (a) the licensed firmware embodied in the Goods will execute the programming instructions provided by Seller; (b) that the Goods manufactured by Seller will be free from defects in materials or workmanship under normal use and care;...
  • Page 5: Table Of Contents

    6.4 Physical specifications........................21 6.5 RoHS directive........................... 22 6.6 Electromagnetic interference (EMI) compatibility..............22 Chapter 7 Product certifications....................23 7.1 ATEX and IECEx.......................... 23 7.2 UK CA............................23 7.3 TR CU............................23 7.4 InMetro............................23 7.5 Certification instructions......................24 Chapter 8 Technical support.....................27 Rosemount FS-UVIR-975...
  • Page 6 Contents Reference Manual May 2022 00809-0800-4975 Emerson.com/Rosemount...
  • Page 7: Chapter 1 Introduction

    Principles of operation The simulator includes a reflector which accumulates the infrared energy and directs it towards the detector. The Rosemount FS-UVIR-975 also includes a sight in order to point the simulator to the center of the flame detector. Rosemount FS-UVIR-975...
  • Page 8: Structure

    The battery compartment includes a battery pack containing four lithium ion batteries of total 14.8 Vdc and 2.6 Ah. Figure 1-1: Flame Simulator side view A. Electronic compartment B. Battery compartment C. Battery compartment cover D. Hand grip E. Reflector F. Push button G. Sight Emerson.com/Rosemount...
  • Page 9 Reference Manual Introduction 00809-0800-4975 May 2022 Figure 1-2: Flame Simulator rear view A. Hand grip B. Reflector C. Sight D. Back cover locking screw Rosemount FS-UVIR-975...
  • Page 10 Introduction Reference Manual May 2022 00809-0800-4975 Figure 1-3: Flame Simulator front view A. Hand grip B. Push button C. Sight Emerson.com/Rosemount...
  • Page 11: Chapter 2 Operation

    Once the trigger is pressed, with an initial two second delay, the equipment will operate for a maximum of 60 seconds, following which the equipment cannot be operated for a minimum period of 30 seconds. Rosemount FS-UVIR-975...
  • Page 12: Simulator Status

    9. Insert the battery into the flame simulator. The LED will flash twice to indicate that the battery is fully charged. 10. Screw in the locking disc using a 1.5 mm hex key. Figure 1-1. 11. Screw in the battery compartment cover. Emerson.com/Rosemount...
  • Page 13: Replace The Battery

    1. To remove the battery, follow Step 1 through Step 5 Charge the battery. 2. Insert the new battery pack into the simulator housing. Use only Rosemount battery pack, PN 00975-9000-0012. 3. Follow Step 9 through Step 12 Charge the battery. Rosemount FS-UVIR-975...
  • Page 14 Operation Reference Manual May 2022 00809-0800-4975 Emerson.com/Rosemount...
  • Page 15: Chapter 3 Troubleshoot

    Recharge the battery. LED flashes three times in five consecutive cycles Recommended actions 1. Disconnect and reconnect the battery. 2. Operate the flame simulator again. LED does not turn on Recommended actions 1. Recharge the battery. 2. Replace the battery. Rosemount FS-UVIR-975...
  • Page 16: Flame Simulator Seems To Work Properly But Does Not Activate The Flame Detector

    1. Verify that you are aiming the flame simulator beam at the center of the flame detector. 2. Verify that you are at the correct distance. 3. Verify that the flame detector is at the correct sensitivity. 4. Verify that the flame detector is operating. 5. Verify that the flame detector is clean. Emerson.com/Rosemount...
  • Page 17: Chapter 4 Maintenance

    Before replacing the battery, ensure that you have a Rosemount battery pack, PN 00975-9000-0012. • When the simulator is not in use, remove the battery pack and recharge every six months. • The typical lithium ion battery lifetime is two to three years under normal conditions. Rosemount FS-UVIR-975...
  • Page 18 Maintenance Reference Manual May 2022 00809-0800-4975 Emerson.com/Rosemount...
  • Page 19: Chapter 5 Ordering Information

    Reference Manual Ordering information 00809-0800-4975 May 2022 Ordering information The kit is supplied in a carry case that includes: • Flame simulator • Charger • Tool kit • Reference manual Rosemount FS-UVIR-975...
  • Page 20 Ordering information Reference Manual May 2022 00809-0800-4975 Emerson.com/Rosemount...
  • Page 21: Chapter 6 Technical Specifications

    Detection ranges per detector/flame simulator Table 6-1: Detection ranges per detector/flame simulator Model Detector types Detector sensitivity Testing distance settings Rosemount FS-UVIR-975 975UR (Legacy) 50 ft (15 m) 8 ft (2.5 m) 975UF (Legacy) 60 ft (20 m) 23 ft (7.01 m) 975UR 93 ft (28 m) 8 ft (2.5 m)
  • Page 22: Rohs Directive

    Immunity to main supply voltage MIL-STD-1275B variations Table 6-3: Emission test Title Basic standard Level to be tested Class Radiated emission IEC 61000-6-3 40 dbuv/m (30 MHz - Like Class B of EN 230 MHz), 55022 47 dbuv/m (230 MHz - 1 GHz) Emerson.com/Rosemount...
  • Page 23: Chapter 7 Product Certifications

    This product is suitable for use in hazardous zones 1 and 2 with IIB + H2 gas group vapor present. TR CU The Rosemount FS-UVIR-975 Flame Simulator is in compliance with the standard TR CU 010/2011 per: 1EX db ib op is IIB + H T5 Gb X -20 °C ≤...
  • Page 24: Certification Instructions

    Ex ib tb IIIC T135 °C Db -4 °F (-20 °C) to 122 °F (50 °C)) The manufacturer/importer/repair site is Emerson at 6021 Innovation Blvd, Shakopee, MN 55379, USA. The equipment may be used with flammable gases and vapors with apparatus groups IIA and IIB + H T4 in the ambient temperature range of -4 °F (-20 °C) to 122 °F (50 °C)).
  • Page 25 The equipment must only be charged in a safe area with the batteries removed from the flameproof enclosure. The charge conditions are as follows: Maximum charge voltage: 16.8 V Maximum charge current: 4 A The charge voltage must not exceed these values. Rosemount FS-UVIR-975...
  • Page 26 Product certifications Reference Manual May 2022 00809-0800-4975 Emerson.com/Rosemount...
  • Page 27: Chapter 8 Technical Support

    Reference Manual Technical support 00809-0800-4975 May 2022 Technical support For all technical assistance or support contact: Emerson Automation Solutions 6021 Innovation Boulevard Shakopee, MN 55379-9795 T +1 866 347 3427 F +952 949 7001 safety.csc@Emerson.com Rosemount FS-UVIR-975...
  • Page 28 2022 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property...