Trane YSJ072A Installation, Operation And Maintenance Manual page 43

Packaged rooftop air conditioners precedent cooling and gas/ electric
Table of Contents

Advertisement

Figure 58. Low voltage wiring — D cabinet
Figure 59. Main control panel low voltage wiring —B/C/D cabinet
Table 7.
Recommended wire lengths
Wire Size
2
AWG
mm
22
0.33
20
0.50
18
0.75
16
1.30
RT-SVX071A-EN
Maximum recommended wire
length from unit controller to
sensor
Meters
Feet
0–46
0–150
47–73
151–240
74–117
241–385
118–185
386–610
Table 7.
Recommended wire lengths (continued)
Wire Size
2
AWG
mm
14
2.00
Note: The total resistance of these low voltage wires must not exceed 2.5
Ω/conductor. Any resistance greater than 2.5 Ω may cause the
control to malfunction due to an excessive voltage drop.
Installation
Maximum recommended wire
length from unit controller to
sensor
Meters
Feet
186–296
611–970
43