Trane YSJ072A Installation, Operation And Maintenance Manual page 28

Packaged rooftop air conditioners precedent cooling and gas/ electric
Table of Contents

Advertisement

Dimensions and Weights
Table 2. Factory installed options (FIOPS)/accessory net weights (lb) (continued)
Accessory
Unit Mounted Disconnect
Notes:
1.
Weights for options not listed are <5 lbs.
2.
Net weight should be added to unit weight when ordering factory-installed accessories.
3.
Weights are approximate.
Lifting and Rigging
WARNING
Heavy Object!
Failure to follow instructions below could result in
unit dropping which could result in death or serious
injury, and equipment or property-only damage.
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings)
may not be of the same length. Adjust as necessary
for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing
operator/technician which could result in death or
serious injury, and equipment or property-only
damage.
Test lift unit approximately 24 inches (61 cm) to verify
proper center of gravity lift point. To avoid dropping of
unit, reposition lifting point if unit is not level.
Figure 27. Rigging and center of gravity — 6 to 12.5
tons
28
YSJ072-120
6, 7.5, 8.5, 10 Tons
5
Figure 28. Rigging and center of gravity — 15 to 25
tons
YSJ150
15, 17.5, 20, 25 Tons
12.5 Tons
5
CENTER OF GRAVITY
LENGTH
YSJ180-300
10
CENTER OF GRAVITY
WIDTH
RT-SVX071A-EN