The controller will automatically return to this screen from any other screen after a period of inactivity.
Alarms Screen
The Alarms (
) screen(s) will display all the alarms, warnings, engine DTC alarms, and the trouble codes. When
an alarm occurs, the controller will automatically jump to this page and will not automatically leave it. The Stop LED
will also flash on and off.
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operator's attention to an undesirable condition. By default, warning alarms are self-resetting when the fault
condition is removed.
Electrical trips are latching and stop the generator in a controlled manner. On initiation of the electrical trip condition,
the controller de-energizes all the outputs, including the lights, to remove the load from the generator. Once this has
occurred, the controller starts the cooling timer and allows the engine to cool off-load before shutting down the engine.
Shutdown alarms are latching and immediately stop the generator. On initiation of the shutdown condition, the
controller de-energized all the outputs, including the lights, to remove the load from the generator. Once this has
occurred, the controller shuts the generator set down immediately to prevent further damage.
Diagnostic Trouble Codes (DTC) alarms are detected by the engine ECU and displayed by the controller.
Fault
Check Engine Fault
Low Oil Pressure
Under Speed
37100 B
AUTO
AUTO
STATUS At Rest
Figure 11 - Home Screen (Manual Mode Shown)
Shutdown
Shutdown
No Alarms
Figure 12 - Alarms screen
Table 2: Possible DTC Faults
The engine ECU has detected a fault not recognized by the con-
troller, contact the engine manufacturer for support.
The engine ECU has detected that the engine oil pressure has
fallen below its configured low oil pressure alarm level.
The engine ECU has detected that the engine speed has fallen
below its configured under speed alarm level.
MDG20IF4-MLG20IF4 Operating Manual
MANUAL
MANUAL
HRS 2 hr
SRV 7 hr
01968
P. 1 / 1
02018
DTC Description
General Information