Water Distribution And Heat Transfer Section; Water Level Control - BAC PCT Series Operation & Maintenance Manual

Cooling towers
Table of Contents

Advertisement

Water Level Control

There are two types of water level controls used on BAC cooling towers:
• Mechanical make-up valve assembly
• Optional electric water level control package
Mechanical Make-up Valve Assembly
A float-operated mechanical water make-up assembly is furnished
as standard equipment on the cooling tower. The standard make-up
assembly consists of a corrosion resistant make-up valve connected to
a float arm assembly actuated by a polystyrene-filled plastic float. The
float is mounted on an all-thread rod held in place by wing nuts. The
cold water basin operating water level can be adjusted by repositioning
the float and all-thread rod using the wing nuts provided.
• Inspect the make-up valve assembly monthly and adjust if necessary.
• Inspect the valve annually for leakage. Replace the valve seat if
necessary.
• Maintain the make-up water supply pressure between 100 and 350
kPa for proper operation. BAC recommends a surge protector
(provided by others) for pressures over 350 kPa.
• Set the initial basin water level by adjusting the wing nuts so
that the make-up valve is completely closed when the water level
in the cold water basin is at the operating level.
• With the design thermal load and the average water pressure
(100 to 350 kPa) at the valve, the above setting will produce
operating water levels as stated in Table 1 on Page 9.
• If the thermal load is less than the design load at the time of
unit start-up, the procedure may produce operating levels greater
than those shown in Table 1. If operating levels are higher than
specified, readjust the float in order to attain the recommended
operating level.
• Closely monitor the water level in the cold water basin and adjust
the level if necessary during the first 24 hours of operation.
• Operating at the recommended water level will ensure that the unit
basin contains sufficient water volume to prevent air entrainment in
the circulating pump during system start-up and provides sufficient
excess basin capacity to accept the total system pulldown volume.
Detailed Component
Maintenance Procedures
Louvres and Eliminators

Water Distribution and Heat Transfer Section

NOTE: If the unit has been
ordered with the optional
electric water level control
package or is intended for
remote sump application, a
mechanical water make-up
valve will not be provided.
Float Arm Assembly
Float Valve
All Threaded Rod
Float Ball
Figure 10. Water Make-Up Valve Assembly
CAUTION: Do not use steam or
high pressure water to clean PVC
eliminators or materials other
than steel.
M A R 1 0 8 - 2
W W W . B A L T I M O R E A I R C O I L . C O M . A U
Wing
Nuts
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pct-1111

Table of Contents