3

Technical description of the burner

3.1

Burner models designation

Model
RS 190/M TC FS1
RS 190/M TC
RS 190/M TC FS1
3.2

Technical data

Model
Output
(1)
Fuel
- Max. delivery
- Pressure at max. delivery
Operation
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
Weight (complete with packaging)
Reference conditions: ambient temperature 68 °F (20°C) - Barometric pressure 394" WC - Altitude 329 ft.
(1)
Pressure at test point 17)(Fig. 4, page 11) with zero pressure in the combustion chamber and maximum burner output.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound power is
(3)
measured using the "Free Field" method, required by EN 15036 standard, and according to an "Accuracy: Category 3" measurement, as described in
EN ISO 3746.
20160742
Technical description of the burner
Riello Code
20160257
20160258
High
MBtu/hr
kW
Low
MBtu/hr
kW
SCFH
"WC
(2)
°F
°F max
dB(A)
lbs
RBNA Code
20166104
208-230/3/60
20166105
20166106
Natural or propane gas
Low - High or modulating
Boilers: water, steam, thermal oil
32 - 104 (0 - 40 °c)
6
GB
Voltage
Flame safeguard
Burner mounted
460/3/60
Burner mounted
575/3/60
Burner mounted
RS 190/M
4845 - 8673
1420 - 2542
1781
522
8673
5.9
140 (60 °c)
83.1
94.1
210
Tab. A