Summary of Contents for Rockwell Automation Allen-Bradley 1606-XLE120B
Page 1
Power Supply - 12V, 10 A, 120 W, Single-phase Input Catalog Number 1606-XLE120B Reference Manual Original Instructions...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Easy Fuse Breaking – 3 times nominal current for 12 ms PLUS • Safe Hiccup Overload Mode • Active Power Factor Correction (PFC) • Minimal Inrush Current Surge • Full Power Between -25… +60 °C (-13…+140 °F) • DC OK Relay Contact Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Size (W x H x D) Without DIN rail (1.26 x 4.88 x 4.02 in) Weight 440 g (0.97 lb) — Catalog Numbers Catalog Number Description 1606-XLE120B 12V, 10 A, 120W Single-phase Power Supply Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
1.5 A 0.95 1.25 a) 100V AC b) 120V AC c) 230V AC 0.75 0.85 (a) 100V AC, (b) 120V AC, (c) 230V AC 0.25 Output Current Output Current 0.75 12 A 12 A Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
180V DC According to IEC 60664-1, continuous operation Earth Turn-on voltage 74V DC Steady state value Shut-down voltage 67V DC Steady state value Figure 5 - Wiring for DC Input Battery Power Supply Load Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Figure 7 - Typical Turn-on Behavior at Nominal Load, 230V AC Input and 25 °C (77 °F) Ambient and 25 °C (77 °F) Ambient Input 50ms/DIV 50ms/DIV Input current current 2A/DIV 2A/DIV Input voltage Input 200V/DIV voltage 200V/DIV Output voltage Output voltage Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
9s before a new start attempt is automatically performed. This cycle is repeated Figure as long as the overload exists. If the overload has been cleared, the device will operate normally. See Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Page 11
A: continuous current B: intermittent current Output Current Output Current 14 16 20 A 50 A PLUS Figure 10 - Short-Circuit on Output, Hiccup Mode, Typical Output Current Normal Normal Short -circuit operation operation Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Minimal permissible load: 1 mA at 5V DC Isolation voltage Dielectric Strength on page Figure 13 - DC OK Relay Contact Behavior 0.9* V < > 1 ms 100 ms 1 ms open closed open closed Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Figure 16 - Efficiency Versus Input Voltage at 12V, 10 A, Typical Figure 17 - Losses Versus Input Voltage at 12V, 10 A, Typical Power Losses Efficiency 11 W Input Voltage Input Voltage 264V AC 264V AC Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
On, when the output voltage is >90% of the adjusted output voltage DC OK Relay Contact The DC OK relay contact is synchronized with the DC OK status indicator. See DC OK Relay Content on page Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Figure 19 - Daisy Chaining of Outputs Figure 20 - Using Distribution Terminals Distribution Terminals Power Power Power Power Supply Supply Supply Supply Load Load Output Output Output Output Max 25 A continuous Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
At 12V, 10 A and 40 °C (104 °F); 68,000 hr 69,000 hr 73,000 hr Ground Fixed GF40 At 12V, 10 A and 25 °C (77 °F); 91,000 hr 93,000 hr 99,000 hr Ground Fixed GF25 Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
10 A 10 A 7.5 A A... 85 to 264V AC, continuous B... short term Altitude 2000 m 5000 m 70 °C 110 kPa 80 kPa 54 kPa Ambient Temperature *) Atmospheric pressure Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
0.20 mA/0.60 mA At 230V AC, 50 Hz, TN-,TT-mains/IT-mains Touch current (leakage current) 0.13 mA/0.35 mA At 110V AC, 50 Hz, TN-,TT-mains/IT-mains 0.17 mA/0.51 mA At 132V AC, 60 Hz, TN-,TT-mains/IT-mains 0.27 mA/0.81 mA At 264V AC, 50 Hz, TN-,TT-mains/IT-mains Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
(1) B: When testing input to DC OK ensure that the maximal voltage between DC OK and the output is not exceeded (column D). We recommend connecting DC OK pins and the output pins together when performing the test. Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Administrative Measures for the Restriction of the Use of RoHS (China RoHS 2) Hazardous Substances in Electrical and Electronic Products 25 years EAC Certificate EAC EurAsian Conformity - Registration Russia, Kazakhstan and Belarus Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
(Example: another power supply). Penetration Small parts like screws with a diameter larger than 5 mm (.20 in.) protection Figure 24 - Front view Figure 25 - Side view All dimensions in mm Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
All dimensions in the following figures are in millimeters. Figure 26 - Isometric Views Figure 29 - Wall/panel Mounting, Side Figure 27 - Wall/panel Mounting, Front View Figure 28 - Hole Pattern for Wall Mounting View Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
32 mm width on the DIN rail. The device does not require an additional auxiliary voltage and is self-powered even in case of a short circuit across the output. Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
At 20 A for 50 ms, resistive load Peak current voltage dips Typically from 12-6V At 50 A for 2 ms, resistive load Typically from 12-5.6V At 50 A for 5 ms, resistive load Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Page 26
Do not use power supplies in series in mounting orientations other than the standard mounting orientation. Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices. Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Page 27
Monitor the individual devices. Therefore, use the DC OK signal of the device. • It is desirable to set the output voltages of all devices to the same value (± 100 mV) or leave it at the factory setting. Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Page 28
Output Output Input Input Input Input Output L N PE L N PE L N PE L N PE Input Input L N PE L N PE 30 A Load 10 A Load Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Page 29
12V, 8 A; (=80%) 12V, 10 A; (=100%) Temperature inside the box 40.7 °C (105.3 °F) 43.2°C (109.8 °F) Temperature outside the box 27.9°C (82.2 °F) 28.0°C (82.4 °F) Temperature rise 12.8 K 15.2 K Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
Page 30
(Horizontal CW - Input on the Left) +70 °C Ambient Temperature Allowed Output Current at 12V 12 A Figure 39 - Mounting Orientation E 6.5 A (Horizontal CCW - Input on the Right) +70 °C Ambient Temperature Rockwell Automation Publication 1606-RM109A-EN-P - August 2020...
12V, 10 A, 120 W, Single-phase Power Supply Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Power Supply Technical Data, publication 1606-TD002. Provides product selection, specifications, and dimensions information. Industrial Components Preventive Maintenance, Enclosures, and Contact...
Page 32
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, FactoryTalk, and Rockwell Automation are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc.