Page 2
(0312) 6775656 to tell you to serve you at all times- Baoding Huazheng Elect ric Manufact ur ing Co. , Lt d. , our company will def initely make you satisf ied !
I. Overview Wireless Zinc Oxide Arrester Tester is a special instrument for on-site and laboratory detection of lightning arrester’s electrical parameters, widely used in on-line monitoring of zinc oxide surge arresters (online test) and laboratory (offline maintenance) test. Meet the People's Republic of China power industry standard "DL474.5-92 field insulation test implementation guidelines - arrester test"...
2、High-precision sampling and processing circuit, advanced Fourier harmonic analysis technology, more reliable data. 3、With the function of measuring harmonic content, it can measure single phase or three phase simultaneously. 4、With resistive current base wave peak output function. 5、The instrument has built-in large storage capacity. Can store test data, waveform, harmonics and other large amount of recording information.
Page 6
(B)Zinc oxide test and menu operation method 1、 After connecting the test line and turning on the power of the instrument, the display interface is shown below: 2、Three-phase test setting interface Press the three-phase test to enter the three-phase parameter setting interface; After setting the parameters, press "Test"...
Page 7
According to the waveform display, display waveform; Display by harmonics, display harmonics: For single-phase test, the file display mode is the same as that for three-phase test. (3) Parameter description: Name: For storage or printing, it is recommended to set before measurement。 Measurement method: 。...
Page 8
the crocodile through the voltage test line, and the other end is connected to the instrument 6-core air seat (voltage input end). Or access through a voltage extension cord. Wireless measurement method: the voltage input is connected to the PT secondary terminal through the alligator clip of the voltage test line, and the other end is connected to the wireless module 6-pin aviation seat (voltage input terminal).
Page 9
Φ0. The instrument gives the conclusion in the table below: result inferior Middle Good Best interference Φ 0~74.99° 75~76.99° 77~79.99° 80~82.99° 83~87.99° ≥88° Note 1: The waveform displayed by the instrument is the collected gear signal, so do not use the waveform amplitude to determine the size of the data. Note 2: No PT measurement, fixed UI angle = 83.5 degrees, easy to calculate resistive current。...
Page 10
Single-phase measurement: (main wiring and three-phase measurement wiring are the same, the wiring of the test product is the phase of which phase is connected, which is not measured.) The detailed wiring of each phase is as follows: 2.1Phase A measurement, the current and voltage lines on the green, red wire clip on the wire hanging, only the corresponding phase A yellow clip.
Page 11
The non-PT measurement method only collects current and only needs to connect the current terminal of the host. (D)System setting and menu operation method: Figure 10 Can clear memory data; Adjust the backlight; Change time; Press the Bluetooth button to pop up the QR code interface, use the mobile phone software to scan the code, you can connect to the mobile phone for remote control;...
V.Precautions 1. In order to use the instrument safely and correctly, please read the instruction manual carefully. Connect and operate according to this manual. 2. Please enter the correct setting parameters before starting the test. 3. The instrument can only be used for low voltage and small current testing, and all leads must be kept away from high voltage.
VII.Packing list Item Low voltage Dedicated test line Black test line Wireless module High voltage Dedicated test line Antenna Charger Ground cable Print paper Fuse pipe...
Need help?
Do you have a question about the HZ-20A and is the answer not in the manual?
Questions and answers