Huazheng HZ-3150A User Manual

Huazheng HZ-3150A User Manual

Transformer dc resistance tester

Advertisement

Quick Links

HZ-3150A
Transformer DC Resistance Tester
USER MANUAL
Huazheng Electric Manufacturing(Baoding) Co.,Ltd

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HZ-3150A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Huazheng HZ-3150A

  • Page 1 HZ-3150A Transformer DC Resistance Tester USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd...
  • Page 2 (0312) 6775656 to tell you to serve you at all times- Baoding Huazheng Elect ric Manufact ur ing Co. , Lt d. , our company will def initely make you satisf ied !
  • Page 3: Table Of Contents

    Contents I. Introduction..............................1 II. Safety Measure............................1 III. Configuration.............................. 1 IV. Technical Data............................2 V. Presentation Of The System........................2 VI. Test And Operating........................... 3 VII. Caution...............................5 VIII. Guarantee and After Sales Service..................... 5 IX. Packing List..............................6...
  • Page 4: Introduction

    I. Introduction The DC resistance is the transformer’s semi-finished product, finished product test, installation, commissioning test, and electric part prevention test necessary test project , the transformer coil can effectively find the device welding, connecting parts loose, missing unit, disconnection, and other manufacturing default and other hidden danger occurred after operation. The DC Resistance transformer to meet fast measurement requirement, we developed HZ-3150 DC Resistance Tester.
  • Page 5: Technical Data

    IV. Technical Data 1、 Output current:<5mA、2.5A、5A、10A、20A 、50A 2、Range: 40μΩ~400mΩ(50A) 100μΩ~1Ω (20A) 500μΩ~2Ω (10A) 1mΩ~4Ω (5A) 2mΩ~8Ω (2.5A) 10Ω-20KΩ ) (<5mA 档 3、Accuracy: 0.2% 4、Resolution:0.1μΩ 5、Operating temperature:0~40℃ 6、Ambient humidity:≤90%RH,(non condensed) 7、Working power:AC220V±10%,50HZ±1HZ V. Presentation Of The System Instrument panel (see the picture): ~220V:Power switch, machine power input, AC socket, safety and switch.
  • Page 6: Test And Operating

    SEL: Setup the current after the tester was reset. press the key for 1-2s to print VI. Test And Operating 1. Connection : Connect the testing product to the device through test terminal, joint firm; meanwhile insure a good connection of the earthing wire. A.
  • Page 7 Measurement device Testing product Pic 5 Measurement device Testing product Picture 3, 4, 5 respectively measure low voltage Rac, Rba, Rcb connection 2. Current options: open the power switch (“I” opens the switch, “O” closes it) meanwhile all the current values will be displayed on the screen, then user can select key for the test products’ current preferences, each time the user press a key, the cursor will roll between the current value of <5mA, 1A, 5A, 10A, 30A.
  • Page 8: Caution

    after selecting the current, press START UP to start the test; meanwhile, the gauge will indicate all the selected current values. When press START UP, few seconds later, it will display "CHARGING", when it displays "TESTING" that means the “CHARGING” has been completed. Few seconds after accessing the TEST STATUS it will show the measured resistance values.
  • Page 9: Packing List

    We provide lifelong maintenance and technology service. If there are abnormalities or faults occur, please timely contact with us, and then we will arrange convenient and fast disposal and field service. IX. Packing List Item Main engine Red test line Black test line Power line Ground lead...