Toshiba Carrier RAV-SP181BT-UL Installation Manual page 24

Air conditioner (split type)
Hide thumbs Also See for Carrier RAV-SP181BT-UL:
Table of Contents

Advertisement

 Check codes and parts to be checked
Wired
Wireless remote control
remote
Sensor block display of
control
receiving unit
Main defective parts
display
Operation Timer Ready
Indication
Flashing
GR
GR
OR
No header remote
control
E01
Remote control
communication trouble
Remote control
E02
transmission trouble
Indoor unit-remote
E03
control regular
communication trouble
Indoor unit-outdoor
unit serial
communication trouble Indoor
E04
IPDU-CDB
communication trouble
Duplicated indoor
E08
addresses
Duplicated header
E09
remote controls
CPU-CPU
E10
communication trouble
Header indoor unit-
indoor follower unit
E18
regular communication
trouble
IPDU communication
E31
trouble
Indoor unit heat
F01
ALT
exchanger sensor
(TCJ) trouble
Indoor unit heat
F02
ALT
exchanger sensor (TC)
trouble
Outdoor unit discharge
F04
ALT
temp. sensor (TD)
trouble
Outdoor unit temp.
F06
ALT
sensor (TE/TS) trouble
F07
ALT
TL sensor trouble
(F06)
Outdoor unit outside
F08
ALT
air temp. sensor
trouble
Indoor unit room temp.
F10
ALT
sensor (TA) trouble
F12
ALT
TS sensor trouble
(F06)
F13
Heat sink sensor
ALT
(L29)
trouble
F15
Temp. sensor
ALT
(F06)
connection trouble
Indoor unit, other P.C.
F29
SIM
board trouble
45-EN
Judging
Parts to be checked / trouble description
device
Incorrect remote control setting --- The header remote
control has not been set (including two remote controls).
Remote
control
No signal can be received from the indoor unit.
System interconnection wires, indoor P.C. board, remote
Remote
control
control
--- No signal can be sent to the indoor unit.
Remote control, network adapter, indoor P.C. board ---
Indoor
No data is received from the remote control or network
adapter.
System interconnection wires, indoor P.C. board,
outdoor P.C. board --- Serial communication trouble
between indoor unit and outdoor unit
Indoor address setting trouble --- The same address as
Indoor
the self-address was detected.
Remote control address setting trouble --- Two remote
controls are set as header in the double-remote control
Remote
control.
control
(* The header indoor unit stops raising alarm and follower
indoor units continue to operate.)
Indoor P.C. board --- Communication trouble between
Indoor
main MCU and motor microcomputer MCU
Indoor P.C. board --- Regular communication is not
Indoor
possible between header and follower indoor units or
between twin header (main) and follower (sub) units.
Outdoor
Communication trouble between IPDU and CDB
Heat exchanger sensor (TCJ) , indoor P.C. board ---
Indoor
Open-circuit or short-circuit of the heat exchanger sensor
(TCJ) was detected.
Heat exchanger sensor (TC), indoor P.C. board --- Open-
Indoor
circuit or short-circuit of the heat exchanger sensor (TC)
was detected.
Outdoor temp. sensor (TD), outdoor P.C. board --- Open-
Outdoor
circuit or short-circuit of the discharge temp. sensor was
detected.
Outdoor temp. sensors (TE/TS), outdoor P.C. board ---
Outdoor
Open-circuit or short-circuit of the heat exchanger temp.
sensor was detected.
TL sensor may be displaced, disconnected or short-
Outdoor
circuited.
Outdoor temp. sensor (TO), outdoor P.C. board --- Open-
Outdoor
circuit or short-circuit of the outdoor air temp. sensor was
detected.
Room temp. sensor (TA), indoor P.C. board --- Open-
Indoor
circuit or short-circuit of the room temp. sensor (TA) was
detected.
TS sensor may be displaced, disconnected or short-
Outdoor
circuited.
Abnormal temperature was detected by the temp. sensor
Outdoor
of the IGBT heat sink.
Outdoor
Temp. sensor (TE/TS) may be connected incorrectly.
Indoor
Indoor P.C. board --- EEPROM trouble
– 23 –
F31
(L29)
Air
H01
conditioner
status
H02
*
H03
H04
*
(P04)
H06
Auto-reset
L03
Auto-reset
L07
L08
Auto-reset
L09
L10
*
(L29)
L20
Auto-reset
Auto-reset
L29
Entire stop
L30
Auto-reset
Auto-reset
L31
Entire stop
P01
P03
Entire stop
P04
Entire stop
P05
Operation
(P04)
continued
P07
Auto-reset
P10
Entire stop
P15
(L29)
Entire stop
P19
(L29)
Entire stop
P20
Auto-reset
(P04)
Outdoor unit P.C.
SIM
Outdoor
Outdoor P.C. board ---- In the case of EEPROM trouble.
board
Current detect circuit, power voltage --- Minimum
Outdoor unit
frequency was reached in the current releasing control or
compressor
Outdoor
short-circuit current (Idc) after direct excitation was
breakdown
detected
Wiring trouble of compressor (open phase)
Outdoor unit
Compressor circuit --- Compressor lock was detected.
Outdoor
compressor lock
Wiring trouble of compressor (open phase)
Current detect circuit, outdoor unit P.C. board ---
Outdoor unit current
Outdoor
Abnormal current was detected in AC-CT or a phase loss
detect circuit trouble
was detected.
Case thermostat
Outdoor
Malfunction of the case thermostat
operation
Outdoor unit low-
Current, high-pressure switch circuit, outdoor P.C. board
pressure system
Outdoor
--- Ps pressure sensor trouble was detected or low-
trouble
pressure protective operation was activated.
Duplicated header
Indoor address setting trouble --- There are two or more
SIM
Indoor
indoor units
header units in the group.
Indoor address setting trouble --- There is at least one
Group line in individual
SIM
Indoor
group-connected indoor unit among individual indoor
indoor unit
units.
Indoor group address
Indoor address setting trouble --- Indoor address group
SIM
Indoor
not set
has not been set.
Indoor power level not
SIM
Indoor
Indoor power level has not been set.
set
Outdoor unit P.C.
In the case of outdoor P.C. board jumper wire (for service)
SIM
Outdoor
board
setting trouble
Network
Address setting, central control remote control, network
LAN communication
adapter
SIM
adapter --- Duplication of address in central control
trouble
central
communication
control
Other outdoor unit trouble
1) Communication trouble between IPDU MCU and CDB
Other outdoor unit
SIM
Outdoor
MCU
trouble
2) Abnormal temperature was detected by the heat sink
temp. sensor in IGBT.
Abnormal external
External devices, outdoor unit P.C. board --- Abnormal
SIM
input into indoor unit
Indoor
stop due to incorrect external input into CN80
(interlock)
Power supply phase sequence, outdoor unit P.C. board -
Phase sequence
SIM
Outdoor
-- Abnormal phase sequence of the 3-phase power
trouble, etc.
supply
Indoor fan motor, indoor P.C. board --- Indoor AC fan
ALT
Indoor unit fan trouble
Indoor
trouble (fan motor thermal relay activated) was detected.
Outdoor unit discharge
A trouble was detected in the discharge temp. releasing
ALT
Outdoor
temp. trouble
control.
Outdoor unit high-
High-pressure switch --- The IOL was activated or a
ALT
pressure system
Outdoor
trouble was detected in the high-pressure releasing
trouble
control using the TE.
The power cable may be connected incorrectly. Check
ALT
Open phase detected
Outdoor
open phase and voltages of the power supply.
Abnormal temperature was detected by the temp. sensor
ALT
Heat sink overheat
Outdoor
of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch circuit,
Indoor unit water
ALT
Indoor
indoor P.C. board --- Drainage is out of order or the float
overflow detected
switch was activated.
There may be gas leakage from the pipe or connecting
ALT
Gas leakage detected
Outdoor
part. Check for gas leakage.
4-way valve, indoor temp. sensors (TC/TCJ) --- A trouble
Outdoor
ALT
4-way valve trouble
was detected due to temperature drop of the indoor unit
(Indoor)
heat exchanger sensor when heating.
High-pressure
ALT
Outdoor
High-pressure protection
protective operation
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
Entire stop
Entire stop
Entire stop
Operation
continued
(thermostat
OFF)
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
(Auto-reset)
Entire stop
46-EN