To Remove The Pinched Pipes - Daikin RKXYQ5T7Y1B Installation And Operation Manual

Vrv iv compressor unit for indoor installation
Hide thumbs Also See for RKXYQ5T7Y1B:
Table of Contents

Advertisement

5 Installation
NOTICE
Pay attention that mentioned torque range is applicable for
opening Ø19.1 mm stop valves only.
To close the stop valve
1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stop
valve clockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now closed.
Closing direction:
To handle the stop valve cover
▪ The stop valve cover is sealed where indicated by the arrow. Take
care not to damage it.
▪ After handling the stop valve, make sure to tighten the stop valve
cover securely. For the tightening torque, refer to the table below.
▪ Check for refrigerant leaks after tightening the stop valve cover.
To handle the service port
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, make sure to tighten the service
port cover securely. For the tightening torque, refer to the table
below.
▪ Check for refrigerant leaks after tightening the service port cover.
Tightening torques
Stop valve
Tightening torque N•m (turn clockwise to close)
size (mm)
Valve body Hexagonal
wrench
Ø9.5
5.4~6.6
4 mm
Ø19.1
27.0~33.0
8 mm
5.3.2

To remove the pinched pipes

WARNING
Any gas or oil remaining inside the stop valve may blow off
the pinched piping.
Failure to observe the instructions in procedure below
properly may result in property damage or personal injury,
which may be serious depending on the circumstances.
Use the following procedure to remove the pinched piping:
1 Remove the valve cover and make sure that the stop valves are
fully closed.
Installation and operation manual
8
Shaft
Cap (valve
Service
lid)
port
13.5~16.5
11.5~13.9
22.5~27.5
a
b
c
d
a
Service port and service port cover
b
Stop valve
c
Field piping connection
d
Stop valve cover
2 Connect the vacuuming/recovery unit through a manifold to the
service port of all stop valves.
You have to recover gas and oil from all 4 pinched pipes. Depending
on your available tools, use method 1 (manifold with refrigerant line
splitters required) or method 2.
Manifold
Connections
A
Method 1:
p <
p >
Connect to all service
B
ports at once.
A
e
B
Method 2:
First connect to the
first 2 service ports.
A
B
Then connect to the
last 2 service ports.
A
B
a, b, c, d
Service ports of stop valves
e
Vacuuming/recovery unit
A, B, C
Valves A, B and C
D
Refrigerant line splitter
3 Recover gas and oil from the pinched piping by using a
recovery unit.
CAUTION
Do not vent gases into the atmosphere.
4 When all gas and oil is recovered from the pinched piping,
disconnect the charge hose and close the service ports.
5 Cut off the lower part of the gas and liquid stop valve pipes
along the black line. Use an appropriate tool (e.g. a pipe cutter,
a pair of nippers).
VRV IV compressor unit for indoor installation
Compressor unit
b
a
C
a
D
b
C
C
c
D
d
C
c
d
C
a
b
C
C
c
d
C
RKXYQ5T7Y1B
4P408443-1 – 2015.07

Advertisement

Table of Contents
loading

Table of Contents