Simplex 4100-5120 Installation Instructions Manual
Simplex 4100-5120 Installation Instructions Manual

Simplex 4100-5120 Installation Instructions Manual

Hide thumbs Also See for 4100-5120:

Advertisement

4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions
Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
EYE SAFETY HAZARD Under certain fibreoptic application conditions, the optical output of this device may exceed eye safety limits. Do
not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
FCC RULES AND REGULATIONS – PART 15. This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA72® after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
NFPA 72® is a registered trademark of the National Fire Protection Association.
Introduction
This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies (TPS). These supplies provide
auxiliary power, a battery charger, and three Signaling Line Circuits (SLC). Each of which provides control and power to the full range of TrueAlert
appliances.
The TrueAlert power supplies are identical to each other with the following exceptions:
• 4100-5120 Domestic (US) version, requires a 120 VAC power source.
• 4100-5121 Canadian version, requires 120 VAC power source and provides battery cutout option. After installing a 4100-5121, refer to
"Enabling Low Battery Cutout Option" in the ES Panel Programmer's Manual (574-849) for information on enabling this option.
• 4100-5122 International version, uses a 220/240 VAC power source.
If you are wiring Class A circuits, you need to install a 4100-5124 Class A Adapter Card onto the TrueAlert Power Supply before installing the power
supply. Refer to Document # 579-337 for more information.
This product is compatible with the 4100U and 4100ES Fire Alarm Control Panel (FACP).
Note: Verify FACP System Programmer, Executive, and Slave Software compatibility when installing, or replacing system components. Refer to the
Technical Support Information and Downloads website for compatibility information.
579-336 Rev. M
*0579336M*

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4100-5120 and is the answer not in the manual?

Questions and answers

Summary of Contents for Simplex 4100-5120

  • Page 1 DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
  • Page 2: Additional Features

    4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Introduction to the TPS The features of the TrueAlert Power Supply are: • Three Signaling Line Circuits. The TPS provides uninterruptible power and control to three separate channels of TrueAlert addressable notification appliances. Each channel is referred to as a Signaling Line Circuit (SLC) and is power limited, power limited is defined in NFPA 70 (National Electric Code).
  • Page 3: Environmental Requirements

    4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Input/Output/Battery Specifications The following table summarizes the AC Input, DC Output, and Battery Charger specifications of the TPS. Table 1: AC Input, DC Output, Battery Charger Specifications AC Input Specifications 4 A Maximum...
  • Page 4: Mounting Procedure

    4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Mounting Procedure The TPS mounts onto the right side of an expansion box, and connects to the Power Distribution Interface (PDI). Slide the two tabs on the bottom of the TPS into the rightmost two slots on the expansion bay.
  • Page 5 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions You must set these switches to the value assigned to the card by the Programmer. Figure 4: DIP Switch SW1 page 5 579-336 Rev. M...
  • Page 6 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Figure 5: Card Addresses Power Distribution Module/Battery Connections The TPS gets its power from the Power Distribution Module (PDM). The PDM takes power directly from a dedicated AC line and the two backup batteries, and distributes power to each bay in the cabinet.
  • Page 7 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Figure 6: PDM/Battery Connections page 7 579-336 Rev. M...
  • Page 8 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Compatible TrueAlert Devices The following table lists compatible TrueAlert devices. All devices are rated one unit load, with the exception of the Isolator Module (4905-9929) that is rated three unit loads. Note: If you are connecting devices to the 4100-5121 (Canadian) TPS, you must only attach TrueAlert compatible, ULC listed devices.
  • Page 9 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Table 3: Compatible TrueAlert Devices Device Installation Document # Audible only horn notification appliances 49AO-WRF 579-1200 49AO-WRF-BA 579-1242 49AO-WRS-BA 49AO-WWF 49AO-WWF-BA 49AO-WWS-BA 49AO-WRS 49AO-WRQ 49AO-APPLC 49AO-APPLC-BA 49AO-APPLW 49AO-APPLW-BA Strobe Multi-Candela (15, 30, 75, 110) Ceiling– Red...
  • Page 10: General Wiring Guidelines

    4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions General Wiring Guidelines • Use only copper conductors for all wiring applications. All equipment must be installed in accordance with the manufacturer's recommendations and the specifications and standards of the authority having jurisdiction (AHJ). The installation of all wiring, cable, and equipment must be in accordance with NFPA 70 and the National Electrical Code (NEC), specifically Article 760 (Fire Alarm Systems), Article 800 (Communications Circuits).
  • Page 11 • Overvoltage suppressors are required when wiring leaves the building. Use Simplex Model 2081-9028 for wire distances of up to 1,000 feet (305 m). Use Simplex Model 2081-9044 for long wire distances and light alarm loads. Note that the 6 Ohm line resistance of Simplex Model 2081-9044 will decrease the distances given in Table 4.
  • Page 12 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions If notification appliances on a given circuit are to be used for multiple notification zones for partial evacuation (selective signaling), then either a Class A loop circuit configuration and isolators must be used, with isolators bounding any wire segment that services a notification zone; or, the NAC riser must be installed in accordance with Survivability From Attack by Fire Requirements in NFPA 2002 ED.
  • Page 13 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Class A Wiring Diagram (No Isolators) Figure 8: Class A Wiring, No Isolators Class A Wiring Diagram (With Isolators) Figure 9: Class A Wiring, with Isolators Note: 4905-9929 isolator. Wiring Class B Circuits Class B Guidelines •...
  • Page 14 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions • All wiring is supervised and power limited. • All wiring to be twisted pair – minimum 18 AWG (0.82 mm²), maximum 12 AWG (3.31 mm²). If shielded pair is used, the cable shield drain wire from all connected branches and taps must attach back to the (--) terminal of the circuit.
  • Page 15 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Class B Wiring Diagram (No Isolators) For Class B wiring with no isolators, T-Tapping is allowed. SLC wiring may be split multiple times to form SLC wiring branches. Maximum wire distance of each of these SLC branches from the panel to any device is the smaller of the values obtained from Table 6 and Table 7. Add the alarm loads of all of the devices on an SLC branch and apply to Table 6.
  • Page 16 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Class B Wiring Diagram (With Isolators) For Class B wiring with isolators, T-Tapping is allowed. SLC wiring may be split multiple times to form SLC wire branches. Maximum wire distance of each of these SLC branches from panel to any device is the smaller of the values obtained from Table 7 and the Equation 1 shown below. Add the alarm loads of all the devices on an SLC wire branch and apply to Equation 1.
  • Page 17 4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions Wiring AUX Power Wiring Diagram to Connect AUX Power to Power Limited Wiring Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to connect a circuit using power-limited wiring, the devices being powered must all be addressable, or a UL Listed EOL relay must be used to supervise the circuit.
  • Page 18: Troubleshooting

    © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).

This manual is also suitable for:

4100-51214100-5122

Table of Contents

Save PDF