Introduction

The 4008/4006-9801 Expansion Power Supply (EPS) is an option module
that installs into the main fire alarm control panel. The EPS provides two
additional NACs, and filtered/regulated 24 VDC, alarm power.
The 3 A alarm power may be split between the two NACs and the
0.5 A auxiliary 24 VDC power tap. Refer to the NAC ratings section of these
instructions for circuit loading restrictions. The expansion power supply is
mounted to the right of the main system board (MSB) at the bottom of the
chassis, and is connected by the installer via three separate harnesses.
One EPS per system is allowed.
Figure 1, below, is an illustration of the EPS assembly.
Figure 1 The Expansion Power Supply
The EPS assembly is shipped with the following:
EPS assembly (bracket with two PCBs)
Screws/washers (441-002; qty: 2)
AC harness (734-179): black/white leads
Battery harness (734-180): red/black leads
Data flex harness (166-438): flat cable
Note: This document contains instructions on installing the EPS into the fire
alarm control panel. For programming instructions, refer to the Front Panel
Installing, Operating, and Programming Instructions (579-704 for 4006, or
579-716 for 4008).
© 2004 Tyco Safety Products, Westminster, MA 01441 USA All specifications were current and are subject to change without notice.
Technical Manuals Online! - http:/ / w ww.tech-man.com
Expansion Power Supply (EPS)
Installation Instructions
System
Compatibility
Operating
Temperature
Operating
Humidity
Dimensions
Current
Rating
AC Input
Voltage
In this Document
Mounting .........................................2
Panel interconnections ...................3
NAC wiring......................................5
Auxiliary 24 V wiring .......................6
NAC ratings ....................................7

Specifications

General
4006/4008 Fire Alarm System
0 to 49 degrees C
32 to 120 degrees F
Up to 93% relative humidity
(non condensing)
Mounting
Width = 4.38 in ( 11.2 cm)
Height = 7 in (17.8 cm)
Depth = 4 in (10.2 cm)
Power
2 A per NAC; 3 A.alarm power
@ 24 VDC
120 V, 60Hz, 2 A max
240 V, 50 Hz, 1.5 A max
PN: 579-707
Rev. A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4008-9801 and is the answer not in the manual?

Questions and answers

Summary of Contents for Simplex 4008-9801

  • Page 1: Specifications

    Expansion Power Supply (EPS) Installation Instructions Specifications General Introduction System 4006/4008 Fire Alarm System Compatibility The 4008/4006-9801 Expansion Power Supply (EPS) is an option module Operating 0 to 49 degrees C Temperature 32 to 120 degrees F that installs into the main fire alarm control panel. The EPS provides two Operating Up to 93% relative humidity additional NACs, and filtered/regulated 24 VDC, alarm power.
  • Page 2 Expansion Power Supply (EPS) Installation Instructions Mounting Mount the EPS to the main annunciation cabinet as shown in the figure below Fasten the EPS to the cabinet with two slotted torx screws (441-002). MAIN CABINET Screwholes Figure 2 Mounting the EPS Technical Manuals Online! - http:/ / w ww.tech-man.com...
  • Page 3 Connect the data flex harness (166-438) from J1 on the EPS to J8 on the 4006-9801 J3 on the 4008-9801 The AC harness (734-179) is used to connect AC power from the MSB to the EPS. AC source is 120 VAC, 60 Hz (single phase) or 240 VAC (nominal), 50 Hz (single phase).
  • Page 4 Expansion Power Supply (EPS) Installation Instructions MAIN SYSTEM BOARD DEPLETED BATTERY CUTOUT JUMPER R407 on 4008 166-438 DATA FLEX R313 on 4006 TOP BOARD HARNESS REMOVE POWER FROM AC AND BATTERY TERMINALS AND FROM CIRCUIT BREAKER P14 on 4008 BEFORE WIRING THE P13 on 4006 EXPANSION POWER SUPPLY.
  • Page 5 Expansion Power Supply (EPS) Installation Instructions NAC wiring CLASS B WIRING: NAC- NAC- MAIN CABINET route NAC wiring upwards 733-894 EOLR MAIN SYSTEM BOARD NAC + NAC + B+ B- • NAC wiring from the EPS is routed within the cabinet as shown above.
  • Page 6 3 A total available from MSB NACs and MSB aux 24 V. 3 A total available from EPS NACs and EPS aux 24 V. • Compatible with Simplex 4098 Series Peripherals; 2098 Series Relay Modules; all Simplex 4090 Series IDNet Peripherals; and 4610-9111 / 4606-9101 Annunciators.
  • Page 7 Synchronization of strobes across all NACs in a system is Candela Notification Appliances. UL Listed for the Simplex models noted in the table For all other UL Listed Notification Appliances, NACs are below. See the table below for maximum number allowed rated Regulated 24 VDC at 1.5 A maximum each.
  • Page 8 Expansion Power Supply (EPS) Installation Instructions DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify the manufacturer. ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs.