Input/Output/Battery Specifications
The following table summarizes the AC Input, DC Output, and Battery Charger specifications of the TPS.
AC Input Specifications
4100-5120/4100-5121
4100-5122
DC Output Specifications
Aux Power and Each SLC
Battery Charger Specifications
Input Voltage Range
Output Voltage
High Voltage Output
Output Current Limit
TPS Current Consumption
Table 2 lists the battery standby requirements for the TPS. The voltage is 24 VDC, which is the rated battery voltage for lead-acid type batteries.
Conditions
Standby – no alarms, SLCs normal
Standby – 3 SLCs ON
Class A option (Standby or Alarm)

Environmental Requirements

The TPS operates normally within the following temperature range: 32° F (0° C) and 120° F (49° C).
Humidity: 90°F (32°C) degrees at 93% Relative Humidity (non-condensing).
Note:
Add auxiliary and card power currents to standby current. For each TrueAlert appliance, add 0.2 mA standby current. The maximum auxiliary current is
2A. The maximum card power is 2A. Deduct card power and auxiliary currents from 9A total power supply capacity.
Maximum power supply alarm capacity is 9A.
page 3
4100-5120, 4100-5121, 4100-5122 TrueAlert Power Supply Installation Instructions
Table 1: AC Input, DC Output, Battery Charger Specifications
4 A Maximum
120 VAC @ 60 Hz
2 A Maximum
220/230/240 VAC @ 50 or 60 Hz
Minimum: 19 VDC
Maximum: 32 VDC
Ripple: 2 VDC, peak to peak @ full load (9A)
21-33 VDC
27.4 VDC ± 500 mV @ 68° F (20° C), temperature compensated at –24 mV / deg. C
29.1 V @ 3.3 A
1.4 A (For 6.2 –18 Ah battery)
3.3 A (Default for 18-50 Ah battery [Canada]; 18-110 Ah battery [United States])
Table 2: Battery Standby
Current
88 mA
100 mA
10 mA