Advertisement

Quick Links

Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15. This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in accordance with
NFPA72® after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100 % tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10 % of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
Introduction
This publication describes the installation procedure for 4100-5101 (120 VAC), 4100-5102 (220 VAC/230 VAC/240 VAC), 4100-5103 (120 VAC with
battery disconnect) Expansion Power Supplies (XPSs), and the 4100-5115 Expansion NAC Module (XNAC). This product is compatible with 4100U and
4100ES fire alarm controls units (FACUs).
Important: Verify FACU system programmer, executive, and slave software compatibility when installing, or replacing system components. Refer to
the Technical Support Information and Downloads website for compatibility information.
Expansion Power Supply Modules
This publication describes the installation procedure for the following:
• 4100-5101 Expansion Power Supply (XPS), 120 VAC, 60 Hz
• 4100-5102 XPS, 220 VAC/230 VAC/240 VAC 50 Hz/60 Hz
• 4100-5103 XPS, 120 VAC, 60 Hz, with battery disconnect (Canada)
• 4100-5115 Expansion NAC Module (XNAC)
The XPS distributes added card power and signal power via the PDI. Signal power is available only in the bay in which the XPS is located. The source of
card power is selected by jumpers P4 & P5 on the PDI.
The XPS includes three NACs, and may be expanded to 6 NACs with the 4100-5115. NACs are wired as Class B or Class A. All circuits are power limited
in accordance with UL 864. The NACs support non-addressable TrueAlert and conventional reverse-polarity operation.
The notification appliance circuits on these modules can be used as regulated 24 VDC circuits, or special application circuits. When used as generic 24
VDC regulated circuits, only 4 Amps of current is available across the three circuits, and any 24 VDC appliance may be attached. When used as special
applications NACs, the full 9 Amps of current is available at the three circuits and only the compatible appliances listed in Table 5 may be connect to
these circuits. The SPS/RPS can synchronize compatible appliances across all three circuits when those circuits are used as special applications NACs.
The XPS has a 9 A capacity. Each NAC is rated at 3 A. A NAC can also be configured as an auxiliary power point, in which case it is rated at 2 A. The
total load at 24 VDC must be no more than 9 A. The total load includes NACs (on the XPS or the XNAC Module), auxiliary power, card power, and signal
power used by modules plugged into the same bay.
Note: If NACs are to be used as auxiliary outputs, they must be configured as such in the Panel Programmer. Programming may also be required for
dedicated auxiliary outputs; refer to the ES Panel Programmer's Manual (574-849).
NACs are monitored for short and open circuits. If a short circuit occurs, the affected NAC will not be energized.
A NAC mis-wiring test, which checks for NACs that are shorted together, can be initiated on command from the operator interface.
AC power and battery backup are provided to the XPS through a connection to the PDM.
Detection of an earth fault on XPS wiring is performed by the SPS, RPS or XBC. Detection is 10k ohm minimum.
The 4100-5103 model is required in jurisdictions, such as Canada, where depleted battery conditions are required by local code to result in power-
down of the unit until AC power is restored. The system must also be programmed for depleted battery cutout for each power supply.
XPS and XNAC Installation Instructions
574-772 Rev. Q
*0574772Q*

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XPS and is the answer not in the manual?

Questions and answers

Summary of Contents for Simplex XPS

  • Page 1 The SPS/RPS can synchronize compatible appliances across all three circuits when those circuits are used as special applications NACs. The XPS has a 9 A capacity. Each NAC is rated at 3 A. A NAC can also be configured as an auxiliary power point, in which case it is rated at 2 A. The total load at 24 VDC must be no more than 9 A.
  • Page 2: Input And Output Specifications

    • LED6 (yellow). Illuminates when communication loss with the CPU occurs. Normally off. *During initialization of the XPS, LEDs 1, 2, and 3 illuminate because the NACs are held in the isolate stage and create an open circuit trouble. Input and output specifications Table 1 summarizes the input and output specifications for the XPS.
  • Page 3 Step 1. Mounting the XPS Guideline The XPS is normally mounted on the rightmost top and bottom positions of the PDI in a 4100 expansion cabinet. Before mounting the XPS, follow these guidelines: • Disconnect power to the system or remove power at the breaker before mounting or installing any modules.
  • Page 4: Setting The Address

    Setting the address The XPS device address is set using DIP switch SW1, which is a bank of eight switches. From left to right, see Figure 3, these switches are designated as SW1-1 through SW1-8. The function of these switches is as follows: •...
  • Page 5 XPS and XNAC Installation Instructions Figure 4: XPS card addresses page 5 574-772 Rev. Q...
  • Page 6: Step 3. Internal Wiring

    Figure 5 shows the PDM in the 4100U/4100ES connecting to a host FACU with two XPSs. Figure 5: System Power The instructions in this section describe how to connect the XPS to AC mains and batteries in both regular 4100U/4100ES back boxes and the 4100-2301 expansion bay (for for non-4100U/4100ES back boxes).
  • Page 7 XPS and XNAC Installation Instructions Power distribution module connections The power distribution module (PDM) connects to the SPS, RPS, or XPS in each bay. One PDM is used for each back box. Use the following instructions to properly connect the PDM to each bay.
  • Page 8 For AC wiring, connect the white and black wires (harness 734-049) from the 120 V and NEUT terminal blocks to the connector at the bottom of the XPS assembly, keeping AC wires at least 1 in. away from all other wires. AC power must be kept to the right side of the cabinet, in the non- power-limited area.
  • Page 9: Class A Nac Wiring Table

    The XPS supports both Class A and Class B NAC wiring. Class A wiring provides a circuit path XPS in the event of a single open circuit somewhere in the loop. Class A wiring requires that two wires are routed from the XPS to each appliance, and then back again to the XPS.
  • Page 10: Class B Nac Wiring Table

    Class B NAC wiring table Table 3 lists the maximum distances from the XPS to the last appliance in a Class B configuration, depending on wire gauge and current. Use Table 3 to calculate wire distances for your application if you are using Class B wiring.
  • Page 11 9th Edition. • When used with the notification appliances listed in Table 4 or Table 5, each NAC is rated for 3 A, and total XPS capacity is rated at 9 A. This rating is the UL864 special application rating. Appliances listed in Table 4 and Table 5 are synchronized in accordance with UL864, between all NACs on the XPS, and any NACs on an SPS, RPS or XPS within the same 4100U/4100ES system, but not if appliances are mixed from both tables.
  • Page 12: Class A Nac Wiring

    To connect the XPS to appliances using Class A wiring, read the following instructions and refer to Figure 11. Route wire (between 12 [3.309 mm²] and 18 AWG [0.8231 mm²]) from the B+ and B- outputs on TB1 of the XPS to the appropriate inputs on a peripheral notification appliance.
  • Page 13: Class B Nac Wiring

    To connect the XPS to appliances using Class B wiring, read the following instructions and refer to Figure 12. Use NAC1, NAC2, or NAC3 to route wire (between 12 [3.309 mm²] and 18 AWG [0.8231 mm²]) from B+ and B- on the XPS to the first appliance.
  • Page 14: Auxiliary Power Wiring

    XPS and XNAC Installation Instructions Auxiliary power wiring The XPS can receive auxiliary power appliances via the dedicated auxiliary power tap (TB2). If additional power is needed, any of the three NAC outputs can be used as auxiliary power inputs.
  • Page 15 Insert plastic standoffs (202-078) and a metal standoff (202-077) to the XPS as shown in Figure 14. Plug J1 on the XNAC into P3 on the XPS using a header (166-549). The holes on the edges of the XNAC should be aligned with the tops of the standoffs.
  • Page 16: Step 6. Troubleshooting

    No Communications with Master For communications to work, the XPS requires a 0 V connection to the PDM. Be sure to attach a fast-on connector to the PC board and also ensure that the fuse in the black battery lead is intact.
  • Page 17 XPS and XNAC Installation Instructions NAC-compatible notification appliances and accessories Table 4: Special application NAC-compatible notification appliancess & accessories Description 4904-9168 V/O 15CD RED FREE-RUN TNA 4904-9171 V/O 15CD WHITE FREE-RUN TNA 4904-9176 V/O 24VDC 15CD RED VER F/S 4904-9177...
  • Page 18 XPS and XNAC Installation Instructions Table 4: Special application NAC-compatible notification appliancess & accessories Description 4903-9252 A/V 24VDC 15CD RED HOR F/S 4903-9253 A/V 24VDC 30CD RED HOR F/S 4903-9254 A/V 24V 110CD RED HOR F/S 4903-9255 A/V 24VDC 15CD RED VER F/S...
  • Page 19 XPS and XNAC Installation Instructions Cooper Wheelock appliances Table 5: Cooper Wheelock appliances Compatible with 4100U/4100ES XPS Wheelock protocol for special applications Synchronizing horn strobes AS-241575W AS Series Horn Strobe. 24V, 15/75Cd, Wall Mount AS-24MCW AS Series Horn Strobe. 24V, Multi-Cd, Wall Mount AS-24MCC AS Series Horn Strobe.
  • Page 20 XPS and XNAC Installation Instructions Table 5: Cooper Wheelock appliances Compatible with 4100U/4100ES XPS Wheelock protocol for special applications STRS STR, Silver Red, 2-Wire, Wall 12/24V, 8Cd, 5 Mount STWS STR, Silver White, 2-Wire, Wall 12/24V, 8Cd, 5 Mount STRC...
  • Page 21 XPS and XNAC Installation Instructions Table 5: Cooper Wheelock appliances Compatible with 4100U/4100ES XPS Wheelock protocol for special applications ET70WPG-2475, ET70WPG-2475 — ET70WPG-2475 , ET70WPB-247 — ET70WPG-2475W, ET70WPR-247 ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt. Green, Blue, Red...
  • Page 22 © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).

This manual is also suitable for:

Xnac4100-51014100-51024100-51034100-5115

Table of Contents