Boss X-POT 6+ Operation & Maintenance Manual page 25

Hide thumbs Also See for X-POT 6+:
Table of Contents

Advertisement

dosInG (ContInued)
3.1. When manual dosing is complete
32. Repeat instructions 1 to 8, 10 to 13.
33. Replace the Cartridge Filter (7) and lower it into the Vessel Body (4) ensuring the
spigot at the bottom of the Cartridge Filter (7) seats into the bottom connection out
of Vessel Body (4).
34. Replace the Baffle Plate (6) and then place it into the Vessel Body (4). Ensure the 4off
pins on the underside of the Baffle Plate locate into the 4off holes in the top of the
Cartridge Filter (7), press down gently to lock the Baffle Plate (6) into the Cartridge
Filter (7).
35. Replace the Magnet Grate (5) back into the Vessel Body (4) on top off the Baffle Plate
(6).
36. Now repeat the operations of 11 to 13, in reverse by following the 'Reassembly After
Inspection' (Section ?) below.
37. Ensure the nuts on the lid have been tightened to a torque of 40Nm.
38. Manually close the ½" Manual Vent Isolating Valve (19) and replace the ½" plug to
prevent accidental opening of the Manual Vent Valve (19).
39. Manually close the 1" Isolating Valve (12). This will close the BOSS™ X-POT6+ Vessel
(4) to drain.
40. Slowly manually open the 1" Isolating Valves (1 & 3) on the Dirty Flow into the BOSS™
X-POT6+. This will now let system water into the BOSS™ X-POT6+ Vessel.
41. At the start of the filling procedure, air will escape through the Automatic Air Vent.
This will be signalled by a 'hissing'. When the air is fully omitted from the vessel...
42. Slowly manually open the 1" Isolating Valves (8 & 11) on the Clean Return from the
BOSS™ X-POT6+.
43. Replace the top cover of the Insulation Jacket and tie.
44. Turn the power on to the BOSS™ X-POT6+ unit by turning the Mains ON/OFF Power
Switch (22) through 90
45. Check to see if the power is on. The power to the VEXO
activate it. The screen should now scroll 'System Pump Run' and the pump will be
operational.
The BOSS™ X-POT6+ has now been used to dose Water Treatment Chemicals, it is back
in operational mode for Side Stream Filtration, it is now active and running in automatic
mode and in-line with the controls philosophy.
BOSS
X-POT6+ Operation & Maintenance Manual (V1.2 September 2017)
TM
.
o
iX-1 Controller (21) will
®
Page 25