vexo
ix-1 ContRoLLeR monItoRInG
®
Volt free contacts are provided for the following conditions. The contacts are rated 5
amp, 230v maximum
Filter On – In Normal Operation, the VEXO
scroll "Filter Pump Run".
The screen
scrolls::
In the event the filter is blocked, the VEXO
scroll "Blocked Filter"
– Filter Blocked, Clean / Replace Filters
The screen
scrolls::
In the event of a Dirty Flow Pressure Transducer failure, the
iX-1 Controller will scroll "Sensor 1 Fail"
VEXO
®
- Pressure Transducer Dirty Flow Failure
The screen
scrolls::
In the event of a Clean Return Pressure Transducer failure, the
VEXO
iX-1 Controller will scroll "Sensor 2 Fail"
®
- Pressure Transducer Clean Return Failure
The screen
scrolls::
In the event the X-POT6+ Circulating Pump fails to operate,
the VEXO
iX-1 Controller will scroll "Pump Fail"
®
– Flow Pump Failure
The screen
scrolls::
1. vexo
No
0
1
2
3
Sensor Maximum Pressure
4
5
6
BOSS
X-POT6+ Operation & Maintenance Manual (V1.2 September 2017)
TM
Filter Pump Run
<
Blocked Filter
<
Sensor 1 Fail
:
<
Sensor 2 Fail
<
Pump Fail
:
<
ix-1 ContRoLLeR PARAmeteRs
®
Parameter
Pressure Differential
Alarm Relay Contacts
Sensor Minimum Pressure
ID Number
Pump Hours
Alarm Count
iX-1 Controller will
®
>
iX-1 Controller will
®
>
>
>
>
Default Value
0.4 Bar
0
0 Bar
10 Bar
0
Range
0.0 – 1.0 Bar
0 = N/C 1 = N/C
0.0 – 10.0 Bar
0.0 – 10.0 Bar
Page 18