[ENG] NetPing Input+Relay 254R304, User Guide -[ENG] [Input+Relay 254R304] 5. Connection of the External Sensors and
[ENG] [Input+Relay 254R304] 5. Connection of the External
Sensors and Executive Devices
It is strictly prohibited to connect sensors and external modules to the Netping devices with power on!
The configuration of the device and receiving notifications from the sensors are in the document "Firmwear
description».

Sensors and devices of the 1-wire model range

The sensors of the 1-Wire model range are connected with 1-wire plugs RJ12 with the possibility to use extension
cords and splitters. The maximum loop length of 1-wire network, connected to one connector is restricted to 50
meters. It is possible to connect up to 2 temperature sensors and 2 humidity sensors  in total at the same time.
To the 1-wire sensors belong:
Temperature sensor 1-wire
Humidity sensor 1-wire (HS)
Sensors of the "dry contact" type 
The number of the connected sensors of the "dry contact" type is restricted by free input lines of a device and total
current consumption of the sensors if they need additional power supply. 
If there is not enough factory cable length, you can extend it using
sequence into each other, or independently using any wire with a cross section of at least 0,4 mm
The maximum permissible length of the cable is 100 meters.

Sensors with two wires

The sensors or other sources of signal, which do not require additional power or they are powered by the other
power sources and it is isolated from the signal line, are connected to the IN terminals and GND terminals of the
device. The polarity of the connection is not important unless otherwise indicated in the documentation for the
device. 
To this type of sensors belong: 
Supply Voltage Sensor 995S2
NetPing Supply Voltage Sensor 995S2
Door sensor metal
Airflow sensor + GRID 120 * 120 * 10mm NC
and other.

Liquid sensor (mod.2605)

This sensor is not an independent device. it is designed to operated together with a special sensitive
(THS);

[ENG] [Input+Relay 254R304] 5. Connection of the External Sensors and Executive Devices

our cables 4 extender,
4m which are connected in
Executive Devices
2
 .
cable.
                             – 