Flue Pressure Switch - Immergas EOLO Mini Manual

24-28 kw special compact wall-hung instantaneous boilers with sealed-room
Hide thumbs Also See for EOLO Mini:
Table of Contents

Advertisement

Technical Documentation

Flue pressure switch (4).

It is located at the top, inside the sealed chamber and, by
means of the relative points, measures the difference in pressure
between the fan output (negative signal) and the inside of
the sealed chamber itself (positive signal).
The signal measured by the pressure switch varies according
to the length of the aspiration/exhaust terminals and can be
measured by the relative pressure points located at the top of
the sealed chamber (9-10).
When this switch trips it causes a contact (S6) to close that
acts on the integrated P.C.B., enabling or preventing burner
ignition.
Intervention pressures
Flue pressure switch
EOLO Mini 24-28 kW
Special
Fan (3).
The extractor works downstream from the combustion cham-
ber and is secured vertically to the top of the hood (2) from
where it extracts the fumes, conveying them to the exhaust
pipes to which the boiler is connected. It guarantees the flow
of air inside the sealed chamber at the same time.
It is controlled by the integrated P.C.B. and basically its ope-
ration coincides with that of the burner.
STEMkW Special ed 01/08
ON
OFF
Head
Head
(mm H
O)
(mm H
O)
2
2
52 (5.3)
42 (4.3)
Technical Documentation
16
EOLO Mini kW Special