Beware of hot surfaces. Some parts, such as heatsinks of power semiconductors, remain hot for a while
after disconnection of electrical supply.
• Keep the drive in its package or protect it otherwise from dust and burrs from drilling and grinding until
you install it.
• Vacuum clean the area below the drive before the start-up to prevent the drive cooling fan from drawing
the dust inside the drive.
Do not cover the air inlet and outlet when
the drive runs.
Make sure that there is sufficient cooling. See the
Quick Start Guide (3AXD50000049129)
Before you connect voltage to the drive, make sure that the doors are closed. Keep the doors closed
during operation.
Before you adjust the drive operation limits, make sure that the motor and all driven equipment can
operate throughout the set operation limits.
Before you activate the automatic fault reset or automatic restart functions of the drive control program,
make sure that no dangerous situations can occur. These functions reset the drive automatically and
continue safe operation after a fault or supply break. If these functions are activated, the installation must
be clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE
STARTS AUTOMATICALLY".
The maximum number of drive power- ups is five in ten minutes. Too frequent power-ups can damage the
charging circuit of the DC capacitors.
If you have connected safety circuits to the drive (for example, emergency stop and Safe torque off),
validate them at the start up. For the validation of the Safe Torque Off, see
firmware manual (3AXD50000016097
instructions provided with them.
ACS580-0P GE SUPPLEMENT [3AXD50000875047]
ACS580-01 Hardware Manual (3AXD50000044794)
for more information.
[English]). For the validation of other safety circuits, see the