Enclosure Fans are thermostatically controlled and will turn on when interior temperature reaches
32oC [90oF]. Enclosure fans will continue to run until the internal temperature of the enclosure drops
below 32oC [90oF] after a normal drive stop. (An E-Stop will remove control voltage, which will disable
the cooling fans.)
Remote Control
Note: Before attempting to run the drive in local, ensure jumpers or additional E-Stop pushbuttons are
installed between terminals CTB1:1 & 2, and between CBT1:2 & 3, CTB1:T1 & T2.
Ensure all necessary parameters are entered into the drive via the ABB Control Panel or Drive Composer.
Before attempting to start the drive, place Hand-Off-Auto Operator(7) in the OFF position, E-Stop pushbutton
(8) is released and the speed potentiometer (9) is set to Zero.
Drive Fault Indicator (5) & Overload Indicator (6) should not be illuminated
Apply power to the drive by turning the Disconnect handle (10) to the ON position. Power On Indicator
(2) should illuminate.
Shortly thereafter, the Drive Ready Indicator (3) should illuminate.
Turn Hand-Off-Auto Operator (7) to the Auto position. Operator should hear output contactor close.
Close the Remote Start contact wired between terminals
CBT1:6 & 7.
Apply 4-20 mA speed reference signal between terminals
CTB1:20 & 21
Running Indicator (4) will illuminate when the Hand-Off-Auto Operator (7) is in the AUTO position
To Stop the drive, open the Remote Start contact wired between terminals CBT1:6 & 7.
Enclosure Fans are thermostatically controlled and will turn on when interior temperature reaches
32oC [90oF]. Enclosure fans will continue to run until the internal temperature of the enclosure drops
below 32oC [90oF] after a normal drive stop. (An E-Stop will remove control voltage, which will disable
the cooling fans.)
ACS580-0P GE SUPPLEMENT [3AXD50000875047]
18